13.1 Setting ranges
[LEnG]
cm
inch
Setting range
10���160
4�0���63
Step increment
0�5
0�2
[OFS]
cm
inch
Setting range
0���100
0���39�4
Step increment
0�5
0�2
The setting ranges for the switching limits (SPx, rPx, FHx, FLx) depend on the
probe length (L)� In general the following applies:
cm
inch
min
max
min
max
SPx / FHx
1�5 (3�5)
L - 3
0�6 (1�4)
L - 1�2
rPx / FLx
1�0 (3�0)
L - 3�5
0�4 (1�2)
L - 1�4
Step increment
0�5
0�2
The values apply if [OFS] = 0� The values in brackets apply to the setting [MEdI] = [LOW]
(setting for the detection of oils and oil-based media)�
•
rPx (FLx) is always lower than SPx (FHx)� If the value for SPx (FHx) is reduced to a value
rPx (FLx), the position of rPx (FLx) also shifts�
•
If rPx (FLx) and SPx (FHx) are close together (approx� 3 x step increment), rPX (FLx) is
changed automatically when SPx (FHx) is increased�
•
If there is a greater distance between rPx (FLx) and SPx (FHx), rPx (FLx) maintains the set
value even if SPx (FHx) is increased�
14 Maintenance
►
Keep the process connection free of deposits and foreign bodies�
►
In case of heavy soiling: clean the process connection and the probe at regular
intervals�
In case of long operation separation layers can form in the medium (e�g� oil on
water)� This applies especially to still pipes or bypasses:
►
Remove separation layers at regular intervals�
►
Ensure that the vent hole (at the upper end of the coaxial pipe) remains free�
►
Keep the interior of the coaxial pipe free from foreign bodies and soiling�