10.7 Changing basic settings
Required after a factory reset [rES] and after changes to the probe or to the
application area�
10.7.1 New entering of the probe length
Approach for single probes:
►
Measure the probe length L to a precision of ± 2 mm (± 0�1 inch)� L =
lower edge of the of process connection to the rod end�
►
Round up the measured value (step increment 0�5 cm / 0�2 inch)�
►
Select [LEnG] and set the value (setting range: 10�0 ��� 160�0 cm / 4�0 ���
63�0 inch)�
Approach for coaxial probes:
►
Measure the total length L
K
of the coaxial probe to a precision of ± 2 mm
(± 0�1 inch)�
►
Deduct 9 mm from the measured value� L = L
K
- 9 mm�
►
Round up the measured value (step increment 0�5 cm / 0�2 inch)�
►
Select [LEnG] and set the value (setting range: 10�0 ��� 160�0 cm / 4�0 ���
63�0 inch)�
Note: After changing the probe length, the values for OFS and the switching
limits must also be reviewed / re-entered�
10.7.2 Setting to another medium
►
Select [MEdI] and set the value:
-[HIGH] for water and water-based media�
-[LOW] for oils and oil-based media�
Note: In case of doubt, carry out an application test to ensure the setting
which is best for your medium�
10.7.3 New entering of the type of probe used
►
Select [Prob] and set the value:
-[rod] for single probe�
-[COAX] for coaxial probe�
•
The detection of water and water-based media is possible with the single
probe as well as with the coaxial probe�
•
The detection of oils and oil-based media is only possible with the coaxial
probe� Therefore, the parameter [Prob] is not available in case of the
setting [MEdI] = [LOW] (the value [COAX] is preset)�