level is reached, this is signalled by the LED OUT1 going out and output 1
switching off�
15.2 Pumping station / empty the tank with overflow protection
Switching output 1: control to empty tank
SP1
Upper value exceeded → submersible pump ON
rP1
Lower value reached → submersible pump OFF
OU1
Hysteresis function, normally open (Hno)
Switching output 2: overflow protection
SP2
Maximum value exceeded → alarm
rP2
Slightly below SP2 (to suppress wave movements)
OU2
Hysteresis function, normally closed (Hnc)
XX�X = display value
A = emptying
B = overflow protection
•
If SP1 is exceeded, output 1 switches (submersible pump ON)� If the level is
below rP1 again output 1 switches off (submersible pump OFF)�
•
If SP2 is exceeded or if there is a wire break, output 2 switches off�