10.2 Basic settings (unit on delivery)
On delivery of the unit, you must first enter the basic settings� The complete
parameter setting menu cannot be accessed before this�
Malfunctions may occur if wrong basic settings are entered�
10.2.1 Entering the probe length
►
Apply operating voltage�
> The initial display
is shown�
►
Change to menu level 2�
►
Select [LEnG], press [Set] for 5 s�
> [nonE] is displayed�
►
Enter the probe length in cm� Remarks on the determination of the probe
length → 10.7.1.
►
Press [Mode/Enter] briefly�
10.2.2 Setting to the medium
►
Select [MEdI], press [Set] for 5 s�
> [nonE] is displayed�
►
Set the requested value:
-[HIGH] for water and water-based media�
-[LOW] for oils and oil-based media�
Note: In case of doubt, carry out an application test to ensure the setting
which is best for your medium�
10.2.3 Entering the type of probe used
►
Select [Prob], press [Set] for 5 s�
> [nonE] is displayed�
►
Set the requested value:
-[rod] for single probe�
-[COAX] for coaxial probe�
•
The detection of water and water-based media is possible with the single
probe as well as with the coaxial probe�
•
The detection of oils and oil-based media is only possible with the coaxial
probe� Therefore the value [COAX] is preset for the parameter [Prob] when
setting [MEdI] = [LOW]; the value [rod] is not available�
Then the unit changes to the operating mode� For further parameter setting the
menu can be opened� The parameters [LEnG], [MEdI] and [Prob] can be accessed
and modified just like all other parameters�