Parameter and EMCY object overview
With the function "restore" (see object directory, index 1011) the parameters
(except the Baudrate and the node ID) can be assigned to the factory default val-
ues. With the next power on they become valid.
Parameterliste
The lifetime factor 0 is interpreted as 1.
The first guard protocol is assessed as "start guarding" even if guarding is not
active at this time (guard time = 0).
INCLINATION SENSOR
CR2101
PAGE
26
Index
default value
Change
Change
Parameter
in object
(factory preset)
automatically
effective
directory
saved
Manufacturer Specific Profile Area; index 2000 to 5FFF
Resolution
2000
0x01 (0.001°)
yes
after Pre-Op
Slope Long Sign
2011
0x00
yes
immediately
PDO 1
(see also housing imprint)
Slope Long Offset
2013
0x00
yes
immediately
Slope Cross Sign
2021
0x00
yes
immediately
PDO 2
(see also housing imprint)
Slope Cross Offset
2023
0x00
yes
immediately
Node ID
20F0, 20F1
0x20 (= 32)
yes
after a reset
Baud rate
20F2, 20F3
0x03 (= 125 Kbits/s)
yes
after a reset
Communication Profile Area; index 1000 to 1FFF
COB ID Synch Objekt
1005
0x80
yes
immediately
Communication Cycle
1006
0x00 (Off)
yes
after Pre-Op
Guard Time
100C
0x00 (Off)
yes
immediately
Lifetime Factor
100D
0x00
yes
immediately
COB ID Guarding
100E
0x700 + Node ID
yes
immediately
COB ID EMCY
1014
0x80 + Node ID
yes
immediately
COB ID Trans PDO 1
1800 01
0x180 + Node ID
no
immediately
Trans Type Trans PDO 1
1800 02
synchronous 1
yes
immediately
COB ID Trans PDO 2
1801 01
0x280 + Node ID
no
immediately
Trans Type Trans PDO 2
1801 02
synchronous 1
yes
immediately