Parameter
Values
Description
Log
Display of the last 100 events
(use ► the ▲ and keys to view
preceding events).
For the first two seconds, the event number (00 for the last
event recorded (= most recent), 01 for the preceding event, and
so on), as well as the date (year-month-day) and time (hours-
minutes-seconds) of creation are displayed.
In the next two seconds, the event description is displayed.
For example:
2 s
Log
00 060324 235034
On 24 March 2006 at 23 hours
(11 p.m.) 50 minutes and 34
seconds…
2 s
Log
Out Of Service
…the apparatus was put out of
service.
2 s
Log
01 060324 235034
View the preceding message
(01) using the ►▲ keys…
2 s
Log
Open Time Out
…we observe that it was put out
of service due to a time out
while opening.
Note
: If no error message is displayed when the machine fails,
refer to the Troubleshooting chapter.
Power Up
Power was turned on.
Power Down
Power was turned off.
Short Circuit
Short circuit of the control board outputs (connector blocks). The
short circuit is declared and the equipment put Out of Service
only after 3 unsuccessful reactivation tries within the 2.5
seconds following a voltage drop in the 24V power supply (this
is to avoid putting it out of service at inopportune moments, as
for example during a network changeover to an emergency
generator).
If one of the outputs short circuits, all of them become inactive
and the control board must be powered up again for the outputs
to be reactivated.
Open Time Out
Time out during opening: the time allocated for opening was
exceeded (TIMING menu, OpenTimeOut parameter).
Close Time Out
Time out during closing: the time allocated for closing was
exceeded (TIMING menu, CloseTimeOut parameter).
Close Retries
Allotted number of trials to close have been executed (as
defined in the TIMING menu).
Arm Swing Off
Arm detected out of its support jaw (see the
Arm Swing Off
parameter in the OPTIONS menu).
If the message continues to be displayed after the arm is
rehinged, check the status of the SW arm presence sensor and
its fastening.
Out Of Service
Apparatus out of service. This may be caused by the following
events:
1) Time out during opening (see
Open Time Out
message).
2) Time out during closing (see
Close Time Out
error) +
allotted number of tries to close have been executed
(see
Close Retries
message).
3) Arm is unhinged (see
Arm Swing Off
message).
4) Locking or unlocking failure of the BL4x (see
Unlock
BL4x Er
message).
5) Defect of the frequency inverter.