IDS 1632 Installer Manual 700-256-02K Issued September 2009
32
9. System Programmable Outputs
Programming the Outputs:
Programmable outputs are able to toggle between different states when specific system events occur.
Either single or multiple events may be programmed to a particular output.
For most events the action of an output, when triggered, is programmable. To program these
events a two digit code must be entered. The output action for certain events is fixed – and function
driven, the strobe function is one example. For these events, only a single digit code need be
programmed.
There are eight programmable outputs on the IDS 1632 Alarm Panels and a further two
programmable outputs on each of the optional Wired Zone Expander modules. When selecting outputs,
programmable outputs on the Alarm Panels are addressed from “1” to “12“.
Outputs on the Wired Zone Expanders are addressed as “9”, “10”, “11” and “12” – (refer to table 5).
Table 5 : Programmable Output Numbering
Value Programmed as
Output Addressed
0
[0]
No Output Addressed
1
[1]
Panel - Programmable Output 1
2
[2]
Panel - Programmable Output 2
3
[3]
Panel - Programmable Output 3
4
[4]
Panel - Programmable Output 4
5
[5]
Panel - Programmable Output 5
6
[6]
Panel - Programmable Output 6
7
[7]
Panel - Programmable Output 7
8
[8]
Panel - Programmable Output 8
9
[9]
Zone Expander 2 - Programmable Output 2
10
[MODE] [0]
Zone Expander 2 - Programmable Output 1
11
[MODE] [1]
Zone Expander 1 - Programmable Output 2
12
[MODE] [2]
Zone Expander 1 - Programmable Output 1
There are 4 permitted output actions that may be selected.
Table 6 : Output Actions
Value
Output Action
0
Set Output High (Set)
1
Set Output Low (Reset)
2
Pulse Output High
3
Pulse Output Low
When programming these outputs a two-digit code must be entered. The first digit references the
programmable output number (Table 5) and the second digit references the output action (Table 6).
Example:
Entering a value of
[1][0]
into location 70 will cause Panel Programmable Output 1 to be set (latched)
high in the event of an AC Mains Failure. Entering a value of
[1][1]
into location 71 will cause the Panel
Programmable Output 1 to be set (latched) low in the event of an AC Mains Restoral.
Summary of Contents for 1632
Page 1: ...IDS 1632 Installer Manual 700 256 02K Issued September 2009 1...
Page 2: ...IDS 1632 Installer Manual 700 256 02K Issued September 2009 2...
Page 6: ...IDS 1632 Installer Manual 700 256 02K Issued September 2009 6...
Page 7: ...IDS 1632 Installer Manual 700 256 02K Issued September 2009 7...
Page 68: ...IDS 1632 Installer Manual 700 256 02K Issued September 2009 68...