Technical data
Te
chnical d
a
ta
Hygienik 2.0
Unit
1000/50
1500/25
1500/35
1500/50
1500/70
Energy ef
fi
ciency class
-
1)
1)
1)
1)
1)
Average power loss
W
99
134
134
134
134
Total storage tank contents
920
1500
1500
1500
1500
Storage tank contents above LSP
2)
l
500
615
615
615
615
Storage tank contents below LSP
l
420
885
885
885
885
Diameter incl. insulation
mm
1018
1170
1170
1170
1170
Height incl. insulation
mm
2170
2400
2400
2400
2400
Installation depth without insulation
mm
Ø790
Ø950
Ø950
Ø950
Ø950
Tilted dimension of tank body
mm
2080
2320
2320
2320
2320
Weight
kg
135
160
165
170
175
Single tapping volume at 45°C
without LSP
2)
l
966
1575
1575
1575
1575
Single tapping volume at 45°C
with LSP
2)
l
524
645
645
645
645
Tapping output
l/min
50
25
35
50
70
Performance index at tank temperature 52°C
-
12
5
10
13
15
Performance index at tank temperature 60°C
-
15
6
12
15
20
Performance index at tank temperature 70°C
-
18
8
15
20
30
Max. residential units
3)
-
18
6
12
20
30
Max. hotel rooms
3)
-
15
6
10
15
25
Max. showers at sport facilities
3)
-
10
5
7
12
18
1)
In accordance with EU Ord. 812/2013 on the energy labeling of hot water storage tanks, there is no energy labeling for hot water storage tanks with a total volume exceeding 500 l
2)
Calculated with:
Storage temperature 60°C
Tapping temperature 45°C
Cold water temperature 15°C
3)
at a storage tank charging temperature of 70°C
The fi gures given for residential units, hotel rooms and sport facilities are reference values for rough planning. For detailed dimensioning,
the corresponding standards and directives must be applied. The fi gures given are based on the following design data:
Residential units:
Each unit equipped with bathtub
Tapping volume per outlet tap: 10 l/min. at 45°C
Simultaneity factor in acc. with Handbuch für Heizung, Lüftung, Klima, Recknagl-Sprenger
Hotel rooms:
Half of the rooms equipped with bathtub, the other half with showers
Tapping volume per bathtub outlet: 10 l/min. at 45°C; per shower: 8 l/min. at 42°C
Simultaneity factor: 1.5 times as high as that given in Handbuch für Heizung, Lüftung, Klima, Recknagl-Sprenger.
Sport facilities:
Tapping volume per shower: 8 l/min. at 42°C
Simultaneity factor: 0.9