MSD-72 series Command Guide
26
@GNP / @SNP
Input position
Getting
Command
@GNP
Response
@GNP, h_position_1, v_position_1, h_position_2, v_position_2
・・・
,
h_position_9, v_position_9
Setting
Command
@SNP, ch_1, h_position_1, v_position_1 (, ch_2, h_position_2,
v_position_2
・・・
)
Response
@SNP, ch_1, h_position_1, v_position_1 (, ch_2, h_position_2,
v_position_2
・・・
)
Parameter
h_position_1-9: Horizontal input position
-Horizontal input size to +Horizontal output resolution [Default] 0
v_position_1-9: Vertical input position
-Vertical input size to +Vertical output resolution [Default] 0
ch_1-9: Input channel
0 = All inputs, 1 = IN1 to 9 = IN9
Getting
example
Command
Response
@GNP
@GNP,-50,20,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0
Description Getting the set input position.
IN1: horizontal input display is -50, vertical input d20
Other inputs: horizontal and vertical input position are 0.
Setting
example
Command
Response
@SNP,1,-50,20
@SNP,1,-50,20
Description Setting IN1 horizontal and vertical input positions are to -50 and +20,
respectively.
Remarks
If resolutions differ depending on output, the OUT1 output resolution will be the
standard.