MSD-701UHD / 702UHD / 801UHD/ 802UHD Command Guide
74
3.3.10 RS-232C communication
@GCT / @SCT
RS-232C communication
Getting
Command
@GCT
Response
@GCT, rs_232c, out_1b, out_2B, in8
Setting
Command
@SCT, port, setting
Response
@SCT, port, setting
Parameter
rs_232cq : Communication setting of RS-232C connector
out_1B
: Communication setting of OUT1B connector
out_2B
: Communication setting of OUT2B connector
in8
: Communication setting of IN8 connector
setting
: Communication setting
・
Baud rate (4800, 9600, 19200, 38400 [bps] [Default] 9600)
・
Data length (8, 7 [bit] [Default] 8)
・
Parity check (NONE, EVEN, ODD [Default] NONE)
・
Stop bit (1, 2 [bit] [Default] 1)
For setting values, see the
.
port: RS-232C channel
0 = All channels,
1 = RS-232C connector,
2 = OUT1B connector,
3 = OUT2B connector,
4 = IN8 connector
Getting
example
Command
Response
@GCT
@GCT,24,24,24,24
Description Getting communication settings of RS-232Cs.
All baud rates = 19200 [bps], data bit length = 8 [bit], parity check = NONE,
stop bit =1 [bit]
Setting
example
Command
Response
@SCT,1,24
@SCT,1,24
Description Setting RS-232C as follows: baud rate = 19200 [bps], data bit length = 8 [bit],
parity check = NONE, stop bit = 1 [bit].
Remarks
For 1-output models (MSD-701UHD and MSD-801UHD), out_2B cannot be set.
For 7-input models (MSD-701UHD and MSD-702UHD), “in8” cannot be set.
“-1” will be sent when these commands are gotten.
If IP address or RS-232C communication setting is changed, the communication
may be disabled. Change the environmental settings based on the MSD settings.