124
NOTE
To exit calibration at any time, touch System Options icon (located in lower left-hand corner
of screen, see Figure 128 thru Figure 130).
D.
Touch check box (located to the right of the instructions text box) when onboard wa-
ter tank is full and you are ready to begin calibration. (see Figure 129).
Figure 129. ITL-40 Calibration Screen
E.
Drain water tank until pump starts to cavitate.
F.
Touch stop icon (see Figure 129).
G.
Stop pump.
H.
Touch Save Button (see Table 3, page 14). Sends calibration to WATER LEVEL ITL-40.
Figure 130. ITL-40 Calibration Screen
I.
If calibration fails, touch Back To Previous Screen icon in upper right-hand corner of
screen, and repeat calibration.
J.
Touch System Options button (see Table 3, page 14).
K.
Cycle SAM system power.