Communication Format
This section describes the communication format for each function code from the slave number up to immediately before the
check code.
Function Code 01 (Read Coil Status) and Function Code 02 (Read Input Status)
Function code 01 reads bit device statuses of Q (output), R (shift register), or M (internal relay). One through 128 consecutive bits
can be read out.
Function code 02 reads bit device statuses of I (input), T (timer contact), or C (counter contact). One through 128 consecutive bits
can be read out.
Communication Frame
Request from Modbus Master
ACK Reply from Modbus Slave
NAK Reply from Modbus Slave
Communication Example
RTU Mode
Purpose
Read 15 bits starting at output Q10.
Q10
(1 – 0)
8 + 0 + 1 = 9
Modbus address: 9
9 – 1 = 8 = 8h
Communication frame address: 0008h
Condition
Slave No. 8
Q10 through Q27 binary data: 1234h
Request from Modbus Master
08 01 0008 0010 (CRC)
ACK Reply from Modbus Slave
08 01 02 34 12 (CRC)
NAK Reply from Modbus Slave
08 81 xx (CRC)
Slave No.
Function Code
Address
No. of Bits
xxh
01h / 02h
xxxxh
xxxxh
Slave No.
Function Code
Quantity of Data
First 8 Bits
Second 8 Bits
Last 8 Bits
xxh
01h / 02h
xxh
xxh
xxh
xxh
Slave No.
Function Code
Error Code
xxh
81h / 82h
xxh
Summary of Contents for SmartAXIS FT9Z-1A01
Page 1: ...FT9Y B1378 7...
Page 10: ...TABLE OF CONTENTS Preface 9 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378...
Page 212: ...7 DEVICE ADDRESSES 7 16 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378...
Page 230: ...8 INSTRUCTIONS FUNCTION BLOCKS REFERENCE 8 18 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378...
Page 344: ...13 SCRIPTS 13 36 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378...
Page 386: ...APPENDIX Appendix 16 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378 Japanese Font JIS X0201...
Page 393: ......