Configure the requests of the Modbus TCP Client.
A maximum of 255 requests can be entered in one request table. Specify the Modbus TCP servers with the remote host numbers.
After all requests are configured, click
OK
button to close the dialog box.
Choose to use Request Execution Devices and Error Status data registers if necessary. When using Request Execution Devices and
Error Status data registers, enter the first number of the devices.
5.
Download the user program to the SmartAXIS.
Programming for the Modbus TCP client is complete. Details about parameters and valid values are as follows.
Function Code
The Modbus TCP of the SmartAXIS supports eight function codes as listed in the table below. Supported function codes and valid
slave addresses vary with each Modbus server device to communicate with. Configure the function codes according to the
specifications of the Modbus server devices.
Function Code
Data Size
Slave Address
SmartAXIS as Modbus Slave
01 Read Coil Status
1 to 128 bits
000001 - 065535
Reads bit device statuses of Q (output), R (shift register), or
M (internal relay).
02 Read Input Status
1 to 128 bits
100001 - 165535
Reads bit device statuses of I (input), T (timer contact), or C
(counter contact).
03 Read Holding Registers
1 to 64 words
400001 - 465535
Reads word device data of D (data register), T (timer preset
value), or C (counter preset value).
04 Read Input Registers
1 to 64 words
300001 - 365535
Reads word device data of T (timer current value) or C
(counter current value).
05 Force Single Coil
1 bit
000001 - 065535
Changes a bit device status of Q (output), R (shift register),
or M (internal relay).
06 Preset Single Register
1 word
400001 - 465535
Changes word device data of D (data register).
15 Force Multiple Coils
1 to 128 bits
000001 - 065535
Changes multiple bit device statuses of Q (output), R (shift
register), or M (internal relay).
16 Preset Multiple
Registers
1 to 64 words
400001 - 465535
Changes multiple word device data of D (data register).
Summary of Contents for SmartAXIS FT9Z-1A01
Page 1: ...FT9Y B1378 7...
Page 10: ...TABLE OF CONTENTS Preface 9 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378...
Page 212: ...7 DEVICE ADDRESSES 7 16 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378...
Page 230: ...8 INSTRUCTIONS FUNCTION BLOCKS REFERENCE 8 18 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378...
Page 344: ...13 SCRIPTS 13 36 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378...
Page 386: ...APPENDIX Appendix 16 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378 Japanese Font JIS X0201...
Page 393: ......