3: I
NSTALLATION
AND
W
IRING
3-14
S
MART
AXIS P
RO
/ L
ITE
U
SER
'
S
M
ANUAL
FT9Y-B1378
Terminal Connection
This section describes types of terminals and how to use them.
When connecting stranded wire or multiple solid wires to a terminal block, use appropriate ferrule for the terminal block.
Terminals for Terminal Blocks
Crimp ferrules using an appropriate tool according to the size of ferrules. Cut the end of the wire to the same length or about 0.5
mm longer than the ferrule.
Ensure that the core wire does not protrude at the end of the shield and there are no whiskers.
The ferrules and crimping tools below can be used.
The recommended ferrules and crimping tools are manufactured by IDEC (top), Weidmüller (middle) or Phoenix Contact (bottom).
Ferrules
Quantity of Cables
Model Number (Order Number)
IDEC
Weidmüller
Phoenix Contact
UL1007 AWG16
For 1-wire
connection
S3TL-H15-14WR (S3TL-H15-14WR)
H1.5/14D SW (9019120000)
H1.5/14 R (0463100000)
AI 1,5-8 BK (3200043)
UL1007 AWG18
For 1-wire
connection
S3TL-H10-14WY (S3TL-H10-14WY)
H1.0/14D R (9019080000)
H1.0/14 GE (0463000000)
AI 1-8 RD (3200030)
For 2-wire
connection
S3TL-J075-14WW
(S3TL-J075-14WW)
H0.75/14D ZH GR (9037410000)
H0.75/14 ZH W (9037230000)
AI-TWIN 2×0,75-8 GY (3200807)
UL1015 AWG22
For 1-wire
connection
S3TL-H05-14WA (S3TL-H05-14WA)
H0.5/14D W (9019010000)
H0.5/14 OR (0690700000)
AI 0,5-8 WH (3200014)
For 2-wire
connection
S3TL-J05-14WA (S3TL-J05-14WA)
H0.5/14D ZH W (9037380000)
H0.5/14 ZH OR (9037200000)
AI-TWIN 2×0,5-8 WH (3200933)
UL2464 AWG24
For 1-wire
connection
S3TL-H025-12WJ (S3TL-H025-12WJ)
H0.25/12T GE (9021020000)
AI 0,25-8 YE (3203037)
Do not touch live terminals, otherwise electrical shocks may be caused.
When the power is on, terminals to which external devices are connected may be heated. Do not touch terminals
immediately after the power is turned off.
Do not touch terminals immediately after the power is turned off, otherwise electrical shocks may be caused.
When connecting a stranded wire or multiple solid wires to a screw terminal block, use a ferrule. Otherwise the wire
may slip off the screw terminal block.
When using ferrules, insert a wire to the bottom of the ferrule and crimp the ferrule.
Caution
0 to 0.5 mm
Damage
Whisker
Correct
Stripped wire is too short
Core wire is visible
2-wire connection
10 to 11 mm
Length of stripped wire
1-wire connection
Cable (AWG 22 to 18)
Cable (AWG 24 to 18)
Single Wire: AWG 16 to 12 (UL)
Stranded Wire: AWG 12 to 14 (JIS)
Summary of Contents for SmartAXIS FT9Z-1A01
Page 1: ...FT9Y B1378 7...
Page 10: ...TABLE OF CONTENTS Preface 9 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378...
Page 212: ...7 DEVICE ADDRESSES 7 16 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378...
Page 230: ...8 INSTRUCTIONS FUNCTION BLOCKS REFERENCE 8 18 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378...
Page 344: ...13 SCRIPTS 13 36 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378...
Page 386: ...APPENDIX Appendix 16 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378 Japanese Font JIS X0201...
Page 393: ......