High-speed Counter Input Specifications
High-speed Counter Output Specifications
Special Internal Relays for High-speed Counter
Note:
Special internal relays M8131 through M8134 go on for only one scan.
Special Data Registers for High-speed Counter
In the first counting cycle, the value stored in D8047 at the second scan is used as a preset value to compare with the cur-
rent value. In subsequent counting cycles, the D8047 value at the moment when coincidence occurred is used as a preset
value for the next counting cycle.
Gate and Reset Inputs for High-speed Counter
Any input or internal relay number can be designated as a high-speed counter gate input and reset input using Function
Area Settings > Others > Enable High-speed Counter in
WindLDR
.
Clearing High-speed Counter Current Value
The high-speed counter current value is cleared to zero in five ways:
when the CPU is powered up,
when a user program is downloaded to the CPU,
when the phase Z or reset-to-zero input at terminal No. 4 is turned on,
when the communication enable button on the CPU module is pressed, or
when the reset input (not the high-speed counter reset input) designated in the Function Area Settings is turned on.
Maximum Counting Frequency
10 kHz
Counting Range
0 to 65535 (16 bits)
Input Voltage
24V DC ±15%
Input Impedance
6 k
Ω
Comparison Output
1 point (terminal 5 on the CPU module)
Output Device
Transistor sink or source output depending on the CPU module type
Output Power Voltage
24V DC ±15%
Output Current
500 mA maximum
Comparison Output Delay
20 µsec maximum
No.
Description
ON
OFF
Operation
R/W
M8010
Comparison Output Reset
Turns off comparison output
—
Continuous
R/W
M8130
Up/Down Status
Counting up
Counting down
Continuous
Read
M8131
Comparison ON Status
Comparison ON
—
ON for 1 scan
Read
M8132
Current Value Zero-clear
Phase Z input ON
—
ON for 1 scan
Read
M8133
Current Value Over flow
Over flow occurred
—
ON for 1 scan
Read
M8134
Current Value Under flow
Under flow occurred
—
ON for 1 scan
Read
M8135
Comparison Output Status
Comparison output ON
Comparison output OFF
Continuous
Read
No.
Description
Updated
Read/Write
D8045
High-speed Counter Current Value
Ever y scan
Read only
D8046
High-speed Counter Reset Value
—
R/W
D8047
High-speed Counter Preset Value
—
R/W
No.
Description
ON
OFF
R/W
Any Input or Internal Relay
High-speed Counter Gate Input
Enables counting
Stops counting
R/W
Any Input or Internal Relay
High-speed Counter
Reset Input
Resets the current value
to the D8046 reset value
—
R/W