![IDEC OpenNet series User Manual Download Page 123](http://html.mh-extra.com/html/idec/opennet-series/opennet-series_user-manual_617384123.webp)
7: B
ASIC
I
NSTRUCTIONS
7-10
O
PEN
N
ET
C
ONTROLLER
U
SER
’
S
M
ANUAL
Timer Accuracy, continued
Timer Counting Error
Every timer instruction operation is individually based on asynchronous 16-bit reference timers. Therefore, an error occurs
depending on the status of the asynchronous 16-bit timer when the timer instruction is executed.
Timeout Output Error
The output RAM status is set to the actual output when the END instruction is processed. So, an error occurs depending on
the timing when the timeout output turns on in a scan cycle. The timeout output error shown below does not include output
delay caused by the hardware.
Maximum and Minimum of Errors
Notes:
Advance error does not occur at the timer input and timeout output.
Tet + Tte = 1 scan time
Increment is 1 sec (TML), 100 msec (TIM), 10 msec (TMH), or 1 msec (TMS).
The maximum advance error is: Increment – 1 scan time
The maximum behind error is: 3 scan times
The timer input error and timeout output error do not include the input response time (behind error) and output
response time (behind error).
Power Failure Memory Protection
Timers TML, TIM, TMH, and TMS do not have power failure protection. A timer with this protection can be devised using
a counter instruction and special internal relay M8121 (1-sec clock), M8122 (100-msec clock), or M8123 (10-msec clock).
Error
TML
(1-sec timer)
TIM
(100-msec timer)
TMH
(10-msec timer)
TMS
(1-msec timer)
Minimum
Advance error
0 msec
0 msec
0 msec
0 msec
Behind error
0 msec
0 msec
0 msec
0 msec
Maximum
Advance error
1000 msec
100 msec
10 msec
1 msec
Behind error
1 scan time
1 scan time
1 scan time
1 scan time
Error
Timer Input Error
Timer Counting
Error
Timeout Output
Error
Total Error
Minimum
Advance error
0 (Note)
0
0 (Note)
0
Behind error
Tet
0
Tte
0
Maximum
Advance error
0 (Note)
Increment
0 (Note)
Increment – (Tet + Tte)
Behind error
1 scan time + Tet
1 scan time
Tte
2 scan times + (Tet + Tte)
Program Processing
Timeout Output RAM
ON
OFF
Actual Output
ON
OFF
END
1 scan time
TIM
END
Tte
Timeout output error is equal to Tte (behind error) and can
be between 0 and one scan time.
0 < Tte < 1 scan time
Tte: Time from the timer instruction execution to the END
processing
Ladder Diagram
I1
I1
ON
OFF
C2
ON
OFF
Timing Chart
10 sec
(10-sec Timer)
CNT
C2
1000
M8123
Reset
Pulse
Prgm Adrs
Instruction
Data
0
1
2
3
LODN
LOD
CNT
I1
M8123
C2
1000
Program List
Note: Designate counter C2 used in this program as a keep type counter. See page 5-3.