TML, TIM, TMH, and TMS (Timer)
Four types of timers are available; 1-sec timedown timer TML, 100-msec timedown timer TIM, 10-msec timedown timer
TMH, and 1-msec timedown timer TMS. A total of 256 timers can be programmed in a user program. Each timer must be
allocated to a unique number T0 through T255.
The preset value can be 0 through 65535 and designated using a decimal constant or data register.
TML (1-sec Timer)
TIM (100-msec Timer)
TMH (10-msec Timer)
TMS (1-msec Timer)
Timer
Allocation Number
Range
Increments
Preset Value
TML (1-sec timer)
T0 to T255
0 to 65535 sec
1 sec
Constant: 0 to 65535
Data registers: D0 to D7999
TIM (100-msec timer)
T0 to T255
0 to 6553.5 sec
100 msec
TMH (10-msec timer)
T0 to T255
0 to 655.35 sec
10 msec
TMS (1-msec timer)
T0 to T255
0 to 65.535 sec
1 msec
I1
I0
T0
Ladder Diagram (TML)
TML
4
T0
I0
ON
OFF
T0
ON
OFF
I1
ON
OFF
Q0
ON
OFF
Timing Chart
4 sec
Prgm Adrs
Instruction
Data
0
1
2
3
4
5
LOD
TML
LOD
AND
OUT
I0
T0
4
I1
T0
Q0
Program List
Q0
I1
I0
T1
Ladder Diagram (TIM)
TIM
20
T1
I0
ON
OFF
T1
ON
OFF
I1
ON
OFF
Q1
ON
OFF
Timing Chart
Prgm Adrs
Instruction
Data
0
1
2
3
4
5
LOD
TIM
LOD
AND
OUT
I0
T1
20
I1
T1
Q1
Program List
2 sec
Q1
I1
I0
T2
Ladder Diagram (TMH)
TMH
100
T2
I0
ON
OFF
T2
ON
OFF
I1
ON
OFF
Q2
ON
OFF
Timing Chart
Prgm Adrs
Instruction
Data
0
1
2
3
4
5
LOD
TMH
LOD
AND
OUT
I0
T2
100
I1
T2
Q2
Program List
1 sec
Q2
I1
I0
T3
Ladder Diagram (TMS)
TMS
500
T3
I0
ON
OFF
T3
ON
OFF
I1
ON
OFF
Q3
ON
OFF
Timing Chart
Prgm Adrs
Instruction
Data
0
1
2
3
4
5
LOD
TMS
LOD
AND
OUT
I0
T3
500
I1
T3
Q3
Program List
0.5 sec
Q3