14: D
ATA
C
ONVERSION
I
NSTRUCTIONS
O
PEN
N
ET
C
ONTROLLER
U
SER
’
S
M
ANUAL
14-11
ATOB (ASCII to BCD)
Valid Operands
For the valid operand number range, see page 6-2.
▲
Internal relays M0 through M2557 can be designated as D1. Special internal relays cannot be designated as D1.
When T (timer) or C (counter) is used as S2, the timer/counter current value is read out. When T (timer) or C (counter) is
used as D1, the data is written in as a preset value which can be 0 through 65535.
Valid values for source S1 data to convert are 30h through 39h. Make sure that the values for each source designated by S1
and the quantity of digits designated by S2 are within the valid range. If the S1 or S2 data is out of the valid range, a user
program execution error will result, turning on special internal relay M8004 and the ERROR LED.
Since the ATOB instruction is executed in each scan while input is on, a pulse input from a SOTU or SOTD instruction
should be used as required.
Valid Data Types
When a bit operand such as I (input), Q (output), M (internal relay), or R (shift register) is designated as the source or des-
tination, 16 points (word data type) are used.
When a word operand such as T (timer), C (counter), D (data register), or L (link register) is designated as the source or
destination, 1 point (word data type) is used.
Operand
Function
I
Q
M
R
T
C
D
L
Constant
Repeat
S1 (Source 1)
ASCII data to conver t
—
—
—
—
—
—
X
X
—
—
S2 (Source 2)
Quantity of digits to conver t
X
X
X
X
X
X
X
X
1-5
—
D1 (Destination 1)
Destination to store conversion results
—
X
▲
X
X
X
X
X
—
—
W (word)
I (integer)
D (double word)
L (long)
X
—
—
—
S1, S1+1, S1+2, S1+3, S1+4
→
D1
When input is on, the ASCII data designated by S1 as many as the
quantity of digits designated by S2 is converted into BCD, and con-
verted into 16-bit binary data. The result is stored to the destination
designated by operand D1.
Valid values for source data to convert are 30h through 39h.
The quantity of digits to convert can be 1 through 5.
ATOB(W)
S1
*****
S2
*****
D1
*****