INSTALL
3.0 SYSTEM SETUP
Luminaire Controllers are easily installed modules that
can turn on/off and dim fixtures and are available as
internal or external mount to allow for junction box or
fixture installation. For maximum flexibility each fixture
can be controlled by a single Luminaire Controller or a
Luminaire Controller can control multiple fixtures as a zone
(see Appendix p. 33 for maximum fixtures per Luminaire
Controller).
As a reminder
, keep track of serial numbers as described
in Section 3.1.1.
Refer to Appendix p. 34 for Luminaire Controller one line
drawings and p. 31 for device information.
The Plug Load Controller is a 20-Amp rated wireless switch
to control power to a typical outlet. This product requires
wiring to be performed per the NEC and local codes
dictated by the AHJ.
WARNING:
Before working on any circuits, verify that
Power is turned OFF to the branch circuit coming into the
outlet box being updated.
3.2.2 LUMINAIRE CONTROLLER INSTALLATION
3.2.3 PLUG LOAD CONTROLLER INSTALLATION
Retro-fit Installation (for single outlet in box)
1. Remove the old device and disconnect the Line and
Neutral wires from device. Keep the ground wire
attached.
2. Disconnect the Line and Neutral wires that were
coming to the device from their pigtail connections.
3. Connect the Plug Load Controller LINE (black) and
NEUTRAL (white) wires to the pigtails that were
connected to the device that was just removed.
These wires are on the side of the device which will
face the box.
4. Re-connect the device to the SWITCHED HOT (red)
and NEUTRAL (white) coming out of the Plug Load
Controller. This side is facing out towards the device.
5. Terminate the wires to the device as required per the
device installation instructions.
6.
IMPORTANT:
Position the Plug Load Controller into
the junction box so the serial number label is facing
toward the outlet.
7. Place “Controlled outlet” sticker on the face of the
outlet.
8. Or use a “Controlled Device” outlet that is properly
marked for this application.
Device side wiring
Plug Load Label Facing Outlet
As a reminder
, keep track of serial numbers as described in Section 3.1.1.
Retro-fit Installations (for single outlet plus branch circuit run continuing from box)
1. Follow same instruction as above, but pigtail the red hot wire to the run traveling to other devices on the same circuit.
2. You may run 2 separate runs that have 1 always HOT and 1 Switched Hot if so desired to the next run on the circuit.
Summary of Contents for Audacy Wireless Controls
Page 1: ...1 OPERATIONS USER MANUAL NOVEMBER 2016 ...
Page 5: ...5 INSTALL ...
Page 17: ...17 CONFIGURE ...
Page 20: ...20 CONTROL ...
Page 27: ...27 APPENDIX ...
Page 34: ...34 APPENDIX F LUMINAIRE CONTROLLER ONE LINE DRAWINGS ESCGRID 1000 PWM LUMINAIRE CONTROLLER ...
Page 42: ...42 APPENDIX G SENSOR COVERAGE PATTERNS WALL MOUNT MODEL VSW 1300 G SENSOR COVERAGE PATTERNS ...
Page 43: ...43 APPENDIX F LUMINAIRE CONTROLLER ONE LINE DRAWINGS CEILING MOUNT MODEL VSC 1300 ...
Page 47: ...47 APPENDIX Duplicate as needed ROOM LOCATION DEVICE TYPE SERIAL ...