Comfosplit IKARO HW
–
User and Installer manual
EN
© Ideal Clima - Page 51 of 68
16.2
DIMENSIONS
CODE
DESCRIPTION
L
[mm]
H
[mm]
P
[mm]
THE01D
COMFOSPLIT IKARO HI-WALL 180 HW INVERTER
850
300
198
THE02D
COMFOSPLIT IKARO HI-WALL 250 HW INVERTER
850
300
198
THE03D
COMFOSPLIT IKARO HI-WALL 350 HW INVERTER
850
300
198
THE05D
COMFOSPLIT IKARO HI-WALL 500 HW INVERTER
850
300
198
THE07D
COMFOSPLIT IKARO HI-WALL 750 HW INVERTER
850
300
198
17
AFTER SALES
17.1
TROUBLESHOOTING
The following pages list the most common causes that may block or cause operation of the unit. The division is
made according to easily identifiable symptoms.
NR
ANOMALY
ANALYSIS OF THE
CAUSES
CORRECTIVE ACTIONS
1
The hydronic terminal
does not work
No electrical power
Check the fuse
Check the Mains socket
Make sure that a timer has not been
enabled
2
Water overflows from the
drain pan
Condensate drain
clogged
Verify that the condensate drain is free.
Insufficient slope of the
condensate drain
pipe.
Verify the slope of the condensate drain.
3
Bad smells
Inadequate
condensation drain
trap
Check that the condensate siphon is
present and properly installed.
4
The fan does not start
The unit is not fed hot
water (in winter) or
cold (in summer)
Verify that the hot or cold-water generator
is in operation and that the circulation is
enabled.
Wait until the battery is hot or cold.
The valve, if installed,
remains closed
Remove the actuator (if present).
Check whether the water flows properly.
Replace the actuator if needed.