When discharging to a wastewater network, perform a small trap to prevent the backflow of smells
towards the environment.
You can use siphons normally used for split air conditioning systems.
If the condensate is discharged in containers or trays, make sure that the exhaust pipe is not
submerged by the condensation, to prevent clogging of the pipe and thus the overflow.
19.4
HYDRAULIC CONNECTIONS
Supply and return water duct exist from the right side of
the unit and end at the center (front view). The pipes are
made of copper DN12 Rc ½ "male fittings. The tubes can
be bent, with caution, to adapt them to the connection
needs.
The flow is marked with
“
IN", the return with
“
OUT". On the
return pipe is fitted and air bleed valve.
To tighten the fittings systematically use two wrenches. To
facilitate the connection, hook the top
IKARO to the mounting plate, and keep it
tilted with the help of a wedge.
19.5
HYDRAULIC KIT
Hydraulic connection kits are available, to be housed in ordinary split-type predisposition fluch boxes, 100 mm
high, or with the more convenient specific predisposition boxes with increased 130 mm height (code TGCL30)
These kits come in both two-way and "three-way execution
Three-way valve kit:
The kit (code TGCL15) consists of:
-
n ° 1 3-way valve with 4 outlets. Kvs = 1.7 in flow-
through and Kvs = 1.3 in by-pass
-
No. 4 copper fittings with double walker ½ "F
-
n ° 8 gaskets
-
n ° 2 extensible hoses ½ "MF
Two-way valve kit:
The kit (code TGCL14) consists of:
-
n ° 1 2-way valve Kvs = 1.7 in flow-through.
-
No. 2 copper fittings with double walker ½ "F
-
n ° 4 gaskets
-
n ° 2 extensible hoses ½ "MF
19.6
UNIT INSTALLATION 'WITH HYDRAULIC KIT
WATER CONNECTION VALVE-SYSTEM
Fit the copper pipes to the valve with walkers and stainless-steel flexible tubes.
Insert the valve, with the connected pipes, in the predisposition box.
For the position and orientation of the pipes, see pictures in the following pages.