82 FAULT FINDING TABLE 2 - Burner Pressure Incorrect or Zero
FAULT FINDING
Notes.
Return to main menu
1.
The burner pressure is regulated by the gas valve, according to the air flow generated by the fan, and on cold
ignition should be slightly higher than the value quoted on the Data Plate.
2.
Equilibrium fan pressures should be as follows: (
± 0.2 mbar) with 300mm flue length
NO
Boiler
Pressure mbar
FF 30
1.6
FF 40
1.7
Boiler
Pressure mbar
FF 50
1.5
FF 60
1.6
Boiler
Pressure mbar
FF 70
0.7
FF 80
1.3
Is the appliance gas cock fully open ?
Contact the
gas supplier
YES
YES
Is the gas supply pressure adequate at the
appliance inlet during an ignition attempt
(i.e. when LED 2 goes OFF) ?
Determine the cause of pressure loss
(e.g. supply pipe too small ?) and rectify
Is the supply pressure
correct at the gas meter ?
YES
Are air and flue ducts free from blockage ?
Clear blockage and take steps to prevent recurrence
NO
YES
Rectify fault and take steps to prevent recurrence
NO
Are the fan and burner pressure sensing pipes
correctly connected, free from damage and
unobstructed by solid matter or moisture ?
Change lead assembly
Check gas valve by substitution
Check for blocked air duct
Check the connections at
the pressure switch.
(wires on 1
and 3) - if OK change the
pressure switch
NO
YES
YES - but only
with the boiler
sealing plate
removed
Is there live on the connector in the control box, which
joins the red lead from the dry fire 'stat to the brown
lead from the gas valve,
during an ignition trial period
?
Remove connectors. With mains OFF, check continuity of
leads from each socket unit back to the corresponding
terminals in the control box. Are leads in good order ?
YES
Can the 'stat be reset when the boiler is cold ?
YES
Has the dry fire thermostat tripped ?
NO
Reset 'stat. Check boiler is
full of water.
Return to main menu
Is there continuity between the terminals of the
dry fire 'stat ?
Are both connectors correctly fitted to the gas valve ?
Has the flue thermostat tripped ?
Can the 'stat be reset when the boiler is cold ?
NO
YES
Is there continuity between the terminals of the
flue 'stat ?
To check the pressure connect an inclined gauge manometer to test points (G) and (I) - refer to Frame 47
YES
NO
Is there live on the red lead of the gas valve connector
on Board 37
during an ignition trial period
?
YES
NO
YES
Check Board 37 by substitution
NO
YES
YES
NO
NO
YES
NO
YES
NO
Replace the flue 'stat.
Return to main menu
Reset 'stat.
Check boiler is full of water.
Return to main menu
Replace the dry fire 'stat.
Return to main menu
F
AUL
T FINDING