FAULT FINDING
Does the fan run correctly ?
Is the correct (or higher) burner pressure
indicated during an ignition attempt ?
Go to Fault Finding Table 2
Has air been purged out of the gas line ?
Is there a spark at the ignition electrodes
during an ignition attempt ?
Go to Fault Finding Table 3
Does the boiler light ?
Go back to Fault Finding Table 3
Go to Fault Finding Table 4
YES
YES
YES
YES
Exit
Go to Fault Finding Table 1
NO
NO
NO
NO
NO
YES
Purge gas line
MAIN MENU
NB: Start the boiler from cold
YES - but only for a few seconds
Note.
The correct sequence of operation during ignition is as follows:-
1.
Mains to boiler with all boiler thermostats calling for heat.
2.
If the fuse on PCB 37 is OK, LEDs 2, 3 and 4 illuminate and the fan starts.
3.
After 8 seconds LED 2 goes OFF, the spark starts and the gas valve opens.
4.
If a flame is detected the spark stops, LED 2 stays OFF and the 'Burner on' neon lights.
5.
If a flame is not detected the spark stops, the gas valve closes, the fan continues to run and LED 2 comes ON.
80 FAULT FINDING CHART
F
AUL
T FINDING