INSTALLATION
ESPRIT 2 -
Installation and Servicing
FLUE OUTLET
33 WATER CONNECTIONS - DHW
1.
The DHW inlet isolating valve incorporates a flow regulator / filter pre-fitted in the valve body Inspect it to ensure no
blockage is evident. Fit it to the DHW inlet ball valve, ensuring the seal provided is correctly located.
2. Fit DHW outlet pipe tail to DHW outlet connection, ensuring the seal provided is correctly located.
32 WATER CONNECTIONS - CH
1.
Connect boiler service valves and copper tails provided in the hardware pack to the threaded boss connections
provided at the lower rear of the boiler. Ensure all boss blanking plugs are removed before connecting hardware. Each
valve must be fitted to the correct boss as shown in the picture. Guidance to correct connection location is also provided
on the wall-mounting template. Ensure each union is fitted with fibre seals provided.
2.
If connecting the boiler to heating loads in excess of 60,000 Btu/h, connecting flow and return heating system
pipework must be sized in 28mm diameter at the point of pipe connection to the boiler tails. Use 22mm x 28mm pipe
adaptors as appropriate.
3.
Do not subject any of the isolating valves to heat as the seals may be damaged.