25 MOUNTING THE BOILER
1.
Before mounting the boiler on the wall place it on its left hand
side and fit ‘S’ trap hose, supplied in the hardware pack.
2.
Locate position of 15mm copper safety drain discharge pipe.
Ensure this pipe is not strained or damaged when mounting the
boiler.
3.
Ensure that the plastic blanking plugs are removed from all of
the boiler service connections before mounting. Note that some
spillage of water may occur when mounting the boiler to the
frame.
nm8764
2
1
3
26 CONNECTING THE FLUE TO THE BOILER
Note.
Before fitting the flue turret fill the condensate trap within the
boiler by pouring a cupful of water into the flue outlet A.
Take care to ensure that the water is only poured into the flue
outlet, and does not spill into the boiler casing.
1.
Locate the flue into the turret.
2.
Insert the flue assembly through the
prepared hole in the wall. Push
through and pull back to seal against
outside wall face.
3.
Locate the flue turret on the top of
the boiler, ensuring that the turret
gasket is in place. Also ensure the
turret is located concentric with the
flue aperture on the boiler top panel.
Check that the flue seal ‘A’ located in
the top of the flue manifold is secure
and giving an effective seal.
4.
Secure the flue turret on top of the boiler
by inserting the open ends of the turret
clamp under the 2 studs and fixing it in the
middle with the single M5 x 10mm pozi-hex
screw provided.
5. Flues over 1 metre long.
Fix the flue support bracket to the wall, using the 4 wall
plugs and wood screws.
NB.
The space bracket will utilise one fixing hole only whilst
used in conjunction with the stand-off option.
4.
Lift the boiler onto the wall mounting frame, locating it
over the tabs at the top of the frame. When handling
the boiler take care not to place strain on safety valve
discharge pipe.
5.
Lower the boiler into position, engaging it onto the
support bracket.
1
2
IMPORTANT: When handling the boiler take
care not to place strain on the safety valve
discharge pipe.