Innovative Circuit Technology Ltd.
45
6. PRODUCT SPECIFICATION
Table 2:
Product Specification for all models
Input Voltage
100 - 265VAC, 50 or 60Hz
Input Power Factor
0.99 Typical
Line Regulation
0.1%
Load Regulation
0.5%
Current Limit
-0/+4% of nominal max limit
Grounding
Positive ground, negative ground, or
floating output allowed
Operating Temperature
Range
-20
C to 60
C
1
Storage Temperature
-40
C to 60
C
EMI
Meets FCC part 15 class B limits
2
Safety
Meets C/UL/EN 60950-1 standard
Efficiency
90% typical
Alarm Relay
Form-C (0.5A, 125Vac max)
Remote Shutdown
(isolated)
External 2V-12V will disable supply
output
1
Derate maximum output 1% per degree C above 50°C ambient
2
This device complies with Part 15 of the FCC Rules, class B limits.
Operation is subject to the following 2 conditions:
This device may not cause harmful interference, and
This device must accept any interference received, including any
interference that may cause undesired operation