6
Innovative Circuit Technology Ltd.
Figure 1: Front Panel Connections
Mount the Front Access Distribution Panel in a 19 inch equipment rack, using
standard rack mounting hardware. (Not provided)
Install appropriately rated circuit breakers in desired channel locations by
carefully inserting a breaker so that its mounting tabs securely snap into the
front panel (with “I/on” marking up). Install the breaker blanking plugs in any
unused locations. Breakers and plugs may be removed by using two small
screwdrivers or similar tools to press in the top and bottom mounting tabs
through the cover openings and gently prying out of the panel.
Label the output channel number of each breaker by applying one of the
supplied labels (A1 to A4, B1 to B4) below each breaker rocker.
WARNING
Risk of serious personal injury or damage to equipment and property! Always
observe the following:
Use an appropriately rated over-current protection device in line with the
main battery connections to the panel
Use an appropriately rated disconnect switch or circuit breaker in line with
the dc inputs to enable installation and service of the panel with the dc
source disconnected
Shut off or disconnect all dc power sources before connecting or
disconnecting wiring
Use wire and connectors rated for the maximum load current and size of
fuse or circuit breaker, and keep cable lengths as short as practical
Carefully observe wiring polarity when making input and output connections
Securely tighten all connections
Bus B Output
Breakers 1-4
Bus B Outputs
Channel 1-4
Bus B Return
(Common)
Bus A Return
(Common)
Site Alarm inputs
1-4, Temp Sense
Bus A, Bus B
Alarm out
C/NC/NO
LAN Port
10/100
Base-T
Bus A Output
Breakers 1-4
Bus A Outputs
Channel 1-4
Bus A Input
(100A cont)
Bus B Input
(100A cont)
Reset button
(recessed)