18
Innovative Circuit Technology Ltd.
Load-Shedding Auto Recovery
: Check this box to allow the output to be
automatically reconnected when the bus voltage is above the
Auto Recovery
Threshold
for at least 60s. The output must be manually re-enabled using
the
Output ON
button on the Status and Control page if the
Auto Recovery
function is not enabled.
Auto Recovery Threshold
: Enter the voltage level at which the selected
output will automatically be reconnected. This value must be at least 0.5V
above the
Load-Shedding Threshold
voltage.
Output Over(Under)-Current Alarm:
Over-Current Threshold
: Enter the over-current level. Output current above
this level for at least 5s will trigger the Over-Current Alarm, and disable the
output (if feature enabled). Disable this alarm by setting the threshold to 0A.
Under-Current Threshold
: Enter the under-current level. Output current
below this level for at least 5s will trigger the Under-Current Alarm. Disable
this alarm by setting the threshold to 0A.
Activate Form-C Contact
: Checking this box will cause the Alarm relay to
trigger for an over(under)-current condition.
Send E-mail
: Checking this box will cause the unit to send an output Current
alarm e-mail to the assigned address entered on the
E-mail Setup
page.
Disable This Output:
Check this box to automatically disable the output for
an Over-Current condition on the selected output. This function may be used
as an electronic circuit breaker which can then be remotely reset by clicking
the
Output ON
button on the Status and Control page.
Network setup
Use this page to configure the network settings for the panel. Click on the Save
Settings button at the bottom of the page to save any changes and re-boot the
panel.
NOTE
:
Saving any changes to the network settings will cause the panel to re-boot,
cycling power to all outputs.
Network:
MAC Address:
Displays the MAC address assigned to the panel
Enable DHCP
: Turn on this setting if your network uses a DHCP server to
automatically assign IP addresses. (Enabled as default setting). To manually