Innovative Circuit Technology Ltd.
Bus Alarm Connector:
(Lower connector plug)
Pin (L-R)
Alarm Function
1
Bus A - Alarm Output common
(0.5A 65Vdc max)
2
Bus A - Alarm Output normally
closed for alarm condition (NC)
3
Bus A - Alarm Output normally
open for alarm condition (NO)
4
No connection
5
Bus B - Alarm Output common
(0.5A 65Vdc max)
6
Bus B - Alarm Output normally
closed for alarm condition (NC)
7
Bus B - Alarm Output normally
open for alarm condition (NO)
Connect up to 4 dry contact type site sensors (such as door/window sensors,
smoke alarm, water detectors etc.) by stripping and terminating 16-28AWG
alarm wiring and connecting to the four Site Alarm Inputs on the 7 pin removable
Site Monitor Plug (upper), if desired. These inputs may be configured to activate
the panel Alarm outputs, or send an alarm e-mail on network connected units.
The external sensor contacts must be voltage free; as a small sense current is
supplied from the panel Alarm Input pins to detect the external contact open or
closed state. Refer to the
Web Based Interface
section for information on how to
configure and use the four Site Alarm inputs.
Connect an optional ICT external temperature sensor (ICT-TMP) to the two TMP
inputs if you need to remotely monitor the temperature of a battery pack or
enclosure.
Site Monitor Inputs:
(Upper connector plug)
Pin (L-R)
Site Monitor Input Function
1
Contact Input 1
2
Contact Input 2
3
Contact Input 3
4
Contact Input 4
5
Monitor Return (common for
4 monitor inputs)
6
Remote Temperature Sense
7
Remote Temperature Sense