Innovative Circuit Technology Ltd.
5
INSTALLATION
Inspect your distribution panel to ensure it was not damaged in shipping, and has
all accessories:
2 clear snap on covers to insulate main dc power connections (shipped
on unit)
4 clear snap on covers for the 4 position output terminal blocks (shipped
on unit)
2 seven pin alarm output, remote sensor input connector plugs (shipped
on unit)
Circuit Breaker label sheet (apply output number label below each
breaker rocker once breakers installed)
This Instruction Manual
To complete the installation you will also need to order circuit breakers
appropriately sized for your requirements, and blanking plugs for any un-used
positions. Order these separately from ICT per the following list:
Breakers:
ICT Model
Rating (65VDC)
Mfg. Part Number
ICT-CB5
5A
Carling MA1-B-14-450-1-A26-2-J
ICT-CB15
15A
Carling MA1-B-14-615-1-A26-2-J
ICT-CB25
25A
Carling MA1-B-14-625-1-A26-2-J
ICT-BLP
Blanking Plug
CBI “B” series rocker handle circuit breakers with 0.25” tab terminals and current
ratings up to 25A may also be used, consult ICT for suitable part numbers.
CAUTION
Risk of personal injury or damage to equipment! Always observe the following:
Install unit in a restricted access location (such as an equipment rack) to limit
unintentional contact with terminals and wiring
Ensure the total power consumption of the loads does not exceed the 100A
(continuous) rated capacity of each power bus
Channel output breakers must not exceed 30A max rating
Install only 65VDC rated breakers
Do not block air inlet or outlet openings in the panel sides and back