Protocol: MB RTU or MB ASCII (MB = Modbus)
Net ID: 1~247
Baud Rate: 1200~115200 bps
Data Bits: 7/8 bits
Stop Bits: 1/2 bits
Parity: None / Odd / Even
5.3.4.2 Device Information
Figure 34: The window of device information
It shows the configuration of the HRT-7(3)10 module. When clicking the left item, it will
show the item data in the right side. About the data of these items is shown as Table 6.
[ Table 6: The data of the node ]
Node
Behavior
Data
HRT-710 click
Module name: HRT-710 / HRT-310
Firmware version: V01.5
System click
Module name: System
[ System: ]
Module count: 0~16
Command count: 0~100
Command interval (ms): 75~65535
Command timeout (ms): 305~65535
Auto Polling: Enable/Disable
HRT-710 / HRT-310 User Manual
Version 1.31
Page
:
49