2.5 DIP Switch
1. HRT-710 :
There is a DIP Switch on the backplane of the HRT-710, as shown in Figure 12.
(1) “Normal” :
[1] The user’s settings will be adapted in HRT-710.
[2] In normal operation, set the DIP Switch to the “Normal” position.
(2) “Default” :
[1] The system default settings will be adapted in HRT-710.
[2] When users forgot the settings of HRT-710 and can’t connect to HRT-710 successfully,
users can set the DIP Switch to the “Default” position and reset HRT-710. Then the
default settings (refer to section 2.5.1) of HRT-710 will be adapted.
Figure 12-1: DIP Switch of the HRT-710
2. HRT-310 :
There are 4 dip-switches on the HRT-310 and these functions are as below.
Item
OFF
ON
Loop PWR
Adapt the external power for HART
loop
(Default)
Adapt the Loop Power for HART loop
(Wiring refer to section 2.7)
Resistor
Disable HART loop resistor
Enable HART loop resistor (Default)
(250 Ohm, 1W)
Default
Adapt the user’s settings (Default)
Adapt the default settings.
(Refer to section 2.5.1)
FW Update
Firmware Operation (Default)
Firmware Update
(Refer to the Q04 of FAQ)
HRT-710 / HRT-310 User Manual
Version 1.31
Page
:
19
Copyright © 2017 ICP DAS Co., Ltd. All Rights Reserved E-mail: [email protected]