ICP DAS, ZT-257x DIO Data Concentrator Quick Start Guide, v1.0
Page 9
Copyright © 2016, by ICP DAS Co., LTD. All Rights Reserved
5.
RF Power: (
-
This parameter is used to configure the strength of the radio frequency signal, as
indicated in the following table.
Code (Hex.)
Description
0x0F
Typical maximum output
0x08
Meets CE/FCC certification
0x00
Typical minimum output
※
Be aware that any adjustment of this parameter is based purely on individual
circumstances. ICP DAS cannot guarantee that the CE/FCC certification will be
applicable if this parameter is adjusted, nor does ICP DAS assume any liability
derived from the illegal adjustment of this parameter.
6.
Trigger Mode: (
-
This parameter is used to modify the trigger type and logic for the DIO channels,
including both the
Level
and the
Pulse
trigger modes.
-
Refer to the user manual for the ZT-20xx-IOG module for more details. Select the
Level Mode
option when using the ZigBee DIO data concentrator function.
7.
Refresh Interval: (
-
This parameter is used to modify the time interval between I/O channel updates (in
seconds).
-
When the DIO state changes from Low to High, one time unit is required for the
updated data to be synchronized.
-
When the DIO state changes from High to Low, two time units are required for the
updated data to be synchronized.