ICP DAS, ZT-257x DIO Data Concentrator Quick Start Guide, v1.0
Page 15
Copyright © 2016, by ICP DAS Co., LTD. All Rights Reserved
3.1.1.
Connecting to the ZT-20xx-IOG Module (RUN)
Step1 Configure the ZT-2570 module to establish a common ZigBee network
with the ZT-20xx-IOG module
①
3.2 Configuring the ZT-257x Module
for details of how to configure the
ZT-2570 module. In order to create a connection between the ZT-2570 module and the
ZT-20xx-IOG module, configure the ZT-2570 module using the settings indicated in the
table below.
②
After completing the configuration, set the DIP switch on the ZT-2570 module to the
“
ZBRUN
”
position, and then reboot the module.
Parameter
ZT-20xx-IOG
ZT-2550
ZT-2570
ZT-USBC
RUN
Pan ID
(ZigBee
Group ID)
User-defined
(Default: 0x0000)
Set to the same ID as the
ZT-20xx-IOG
Node ID (*)
ZigBee Router
ZigBee Coordinator
Set using DIP switches 4-8.
The Node ID can be set a value in
the range of
0x0001 to 0x001F
Hardware Settings of for the
ZT-20xx-IOG Module
for more
information regarding
the positions
of
DIP Switches 4-8)
0x0000
RF Channel (*)
Set using the Rotary switch (0 - F)
Set to the same frequency as
the ZT-20xx-IOG
Application Mode (*)
Level Mode
Level
Mode/Transparent
Mode
N/A
Data Format
N/A
None, 8, 1
Baud Rate
N/A
115200 bps
Note that the Pan ID must be the same for all modules that exist in the same ZigBee network.
(*): See item2 in step 2 below.