ICP DAS, ZT-257x DIO Data Concentrator Quick Start Guide, v1.0
Page 13
Copyright © 2016, by ICP DAS Co., LTD. All Rights Reserved
3.1
Configuring the ZT-20xx-IOG Module
Establishing ZigBee Wireless Communication
As the ZT-20xx-IOG module has no physical communication port,
a ZigBee wireless
connection needs to be established using the ZigBee convertor (e.g., ZT-2570, ZT-2550, or
ZT-USBC) in order to configure the ZT-IOG module via wireless communications
.
There are three main parameters that need to be configured are shown below.
Parameters
ZT-20xx-IOG
ZT-2550/
ZT-2570
ZT-USBC
Value
(1) Pan ID
Set via software
Set via software
Set to the same value
(2) Node ID
Set via DIP Switch
Set via software
Set to a unique value
(3) RF Channel
Set via Rotary Switch
Set via software
Set to the same value
-
The
Node ID
and
RF Channel
for the ZT-20xx-IOG module are set using either the DIP or
the Rotary switch. See Section
3.1.3 Hardware Settings for the ZT-20xx-IOG Module
details of how to create a ZigBee wireless connection.
-
The
Pan ID
for the ZT-20xx-IOG module is set remotely using software and cannot be
adjusted using an external hardware switch. There are two methods of creating a
connection between the ZT-2570 module and the ZT-20xx-IOG module:
①
If the Pan ID
is known
: Set the ZT-20xx-IOG module to
RUN
mode, and then configure
it remotely via wireless communication using a ZT-2570 module.
②
If the Pan ID
is unknown
: Set the ZT-20xx-IOG module to
INIT
mode, and then
configure it remotely via wireless communication using a ZT-2570 module.
※