ICP DAS, ZT-257x DIO Data Concentrator Quick Start Guide, v1.0
Page 17
Copyright © 2016, by ICP DAS Co., LTD. All Rights Reserved
3.1.2.
Connecting to the ZT-20xx-IOG Module (INIT)
Step1
Configure the ZT-2570 module to establish a common ZigBee network
with the ZT-20xx-IOG module
①
In order to create a connection between the ZT-2570 module and the ZT-20xx-IOG
module, configure the ZT-2570 module using the settings indicated in the table below.
3.2 Configuring the ZT-257x Module
for details of how to configure the
ZT-2570 module.
②
After completing the configuration, set the DIP switch on the ZT-2570 module to the
ZBRUN
position, and then reboot the module.
Parameter
ZT-20xx-IOG
ZT-2550
ZT-2570
ZT-USBC
INIT
Pan ID
(ZigBee Group ID)
0x3FFF
Set to the same ID as the
ZT-20xx-IOG
Node ID (*)
ZigBee Router
ZigBee Coordinator
0x0020
0x0000
RF Channel (*)
Set using the Rotary switch (0 - F)
Set to the same frequency as
the
ZT-20xx-IOG
Application Mode (*)
Level Mode
Transparent Mode
N/A
Data Format
N/A
None, 8, 1
Baud Rate
N/A
115200 bps
Note that the Pan ID must be the same for all modules that exist in the same ZigBee network.
(*): See item2 in step 2 below.
Step2 Configure the ZT-20xx-IOG module via the ZT-2570 module
①
Set the DIP switch on the ZT-20xx-IOG module
to the “
INIT
” position (i.e., move DIP
switch 1 to the ON position).
②
Configure the ZT-20xx-IOG module, and then adjust the hardware switches based on
the
Node ID, RF Frequency and Application Mode
settings indicated in the table above
.
3.1.3 Hardware Settings for the ZT-20xx-IOG Module
adjust the ZT-20xx-IOG module.