AM335X-PAC Series User Manual version 2.0.1 Page: 17
Copyright © 2019 ICP DAS Co., Ltd. All Rights Reserved. E-mail: [email protected]
Step 3: Connect the ground lead to
the frame ground point.
Tips & Warnings
A good common ground reference (earth ground) is essential for proper
operation of the LP-9x2x. One side of all control circuits, power circuits, and the
ground lead must be properly connected to earth ground by either installing a
ground rod in close proximity to the enclosure or by connecting to the incoming
power system ground. There must be a single-point ground (i.e. copper bus bar)
for all devices in the enclosure that require an earth ground.
DIN-Rail mounting
Step 1: Fasten the DIN-Rail clip to the LP-9x2x.