I-8017/I-9017 Series I/O Module User Manual
V3.0.3
P.74
Step 3:
Calibrate
After execute the program, select the range that needs to be calibrated and press the number
corresponding to the range.
Output stable positive source to channel 0, and type the value displayed on the voltage meter.
Output stable negative source to channel 0, and type the value displayed on the voltage meter.
Press ‘y’ to save new gain and offset values