Return Values
Others: Refer to Appendix A: “Error Code” for more details.
Note
I-8017HW series modules equipped with a 14-bit AD chip.
This function will calibrate the data that read from the chip and convert it into 16-bit data.
The following pictures show the scale of voltage and data and how to calculate the
hexadecimal data into floating data.
If(hexadecimal data >=0)
floating data = (hexadecimal data /
32767
) * 10
Else
floating data = (hexadecimal data /
32768
) * 10
If(hexadecimal data >=0)
floating data = (hexadecimal data /
32767
) * 5
Else
floating data = (hexadecimal data /
32768
) * 5