ET-2200 Series Ethernet I/O Modules
Copyright © 2020 ICP DAS CO., Ltd. All Rights Reserved.
-54 -
The following table provides an overview of the parameters contained in the
I/O Pair-Connection
Settings
section:
Item
Description
Default
Mode
This parameter is used to define the Server mode for the ET-2200 series
module.
Mode = Disable
: Server mode (Slave).
Mode = PULL
: Pull remote DI to local DO in the Client mode (Master).
Mode = PUSH
: Push local DI to remote DO in the Client mode (Master).
The DI Count field must also be configured to enable Client mode.
Disable
Remote IP
The IP address of the remote device to access.
0
Remote Port
The TCP port number of the remote device to access.
Range: 0 to 65535.
502
Net ID
The Modbus Net ID of the remote device to access.
Range: 1 to 247.
1
Scan Time
For
“PULL”
mode, the module will update the DI/DO states based on the
time period of the Scan Time parameter.
For
“PUSH”
mode, the module will update remote DO state when the local
DI state is changed. The module will also force update remote DO when
the local DI is no change during the time period of the Scan Time
parameter.
Range: 1000 to 42949672965 ms.
1000 ms
DI Count
This parameter specifies how many digital I/O channels are mapped.
Range: 1 to 16; 0= Disable.
0
DI Addr
For
“PULL”
mode, this parameter specifies the base address of the
Remote
DI device
that will be mapped to the
Local DO register
. The range depends
on the type of remote device being used.
For
“PUSH”
mode, this parameter specifies the base address of the
Local
DI register
that will be mapped to the
Remote DO device
. The range
depends on the type of ET-2200 module being used.
0