![background image](http://html1.mh-extra.com/html/icp-das-usa/et-2200-series/et-2200-series_user-manual_3606719014.webp)
ET-2200 Series Ethernet I/O Modules
Copyright © 2020 ICP DAS CO., Ltd. All Rights Reserved.
-14 -
ET-2254/2254P
Model
ET-2254
ET-2254P
I/O Type
By Wire Connection, Configurable Universal DIO
I/O Channels
16
Digital Input
Type
Dry Contact
Sink/Source (NPN/PNP)
Source
On Voltage Level
Close to GND
Off Voltage Level
Open
Input Impedance
3kΩ, 0.5 W
7.5kΩ, 1 W
Counters
Max. Count
4,294,967,295 (32 bits)
Max. Input Frequency
3 kHz
2.5 kHz
Programmable Digital Filter
1 ~ 6500 ms (0.08 Hz ~ 500 Hz)
Digital Output
Type
Open-collector (Sink)
Max. Load Current
100 mA/channel
400 mA/channel
Load Voltage
+5 V
DC
to +30 V
DC
+5 V
DC
to +50 V
DC
Short Circuit Protection
-
Yes
Power-on Value
Yes, Configurable
Safe Value
Yes, Configurable