Technical specification:

 

 

 

Type:  

 

UWI-IQ 

 

 

Software: 

 

UWI V40.009 & IQRF V41.002/OS4.00

 

Purpose: 

 

 

 

 

 

Transmission of two input signals from one UWI-IQ by wireless to two relay outputs and loop  

 

 

 

 

 

option of the second UWI-IQ unit, which is configured into the  wireless link (peer to peer) or to uCU-IQ system by  

 

 

 

compatible communication protocol and messages.

 

 
Wireless communication: 

868 MHz band, recommended channel in the range from 56 to 60

 

 

 

UWI-IQ wireless loop (PEER to PEER net) or configuration into a system with  the wireless control panel 

µ

CU-IQ 

 

 

 

(STAR net wireless system configuration)

 

 

 

ICAS wireless communication protocol, zone supports, ICAS MASH architecture support, 

 

 

 

compatible with 

µ

CU-IQ,

 

 

 

certified IQRF radio-module

 

 

 

compatible to RF monitor PC tool for configuration and monitoring

 

 

 

variants with internal or external antennas

 

 
Recommended ext. antenna:        868 MHz 5dBi whip 

 

 

 

 

Power: 

  

External power supply voltage in the range  from 9V to 24V DC 

 

 
Current consumption standby: 

 < 5 mA (Normal - only green Led indication)

 

Max. current consumption:  

<  90mA (Test mode+local alarm +local fault -all leds lighting, both relays on and loop output in fire alarm)   

 

 
 
Testing 

 

ByTest/Reset push-button - the short press from  Normal will trig a TEST mode - Test Leds is lighting ,test message (T) is 

 

sent by SPI and forwarded by the radio-module.  The radio-communication range can be tested this way

 

 

 

By long press of the TEST/RESET push button / till lit of both red and yellow at the same time/ set Diagnostic mode and  

 

Local Alarm/Fault will control in Diagnostic  mode also the unit outputs /relays and loop output/. The inputs and outputs 

 

response can be tested without radio-communication or without configuration into a system this way

 

 
Delay/input filter: 

 

Adjustable delay - pre-alarm period in steps 4s, default set is 2 samples of pre-alarm. 

 

Output delay 

 

Adjustable delay from alarm/fault message receiving to outputs activation in steps 4s (default set is 0)

 

 
Configuration into system : 

By the RF monitor V.16 and higher ( PC application) and DS-IQ module 

 

 

Configurable parameters:  

By the  RF monitor PC tool  (UWI-IQ Setting page)

 

 

Input delay 

 

255 steps ( one step is about 4s)   

Default 2 

 

Output delay   

255 steps ( one step is about 4s)   

Default 0

 

INP 1 (Fire input)   level  Normal open / Normal closed 

 

Default NO 

 

INP 2 (Fault input) level  Normal open / Normal closed 

 

Default NO 

 

Q response 

 

Disabled / Enabled 

 

 

Default Disabled

 

Hush response   

Disabled / Enabled 

 

 

Default Disabled

 

 
TEST / RESET button:   

Serves for control of  TEST, RESET, RESTART, HUSH, DIAGNOSTICS mode and  INPUT DELAY set (without PC tool) 

 
Temp. : 

 

-10 

o

C to +55 

o

C

 

Humidity:   

 

95%RH (No condensation)

 

Size (without ext. Antenna): 

85 mm  x  85 mm x 43 mm

 

 
 
 

Summary of Contents for UWI-IQ

Page 1: ...UWI IQ manual rev 5 07 2019 Page 1 12...

Page 2: ...UWI IQ manual rev 5 07 2019 Page 2 12 UWI IQ Universal wireless interface in the band 868 MHz Universal wireless link UWI IQ to UWI IQ D R A F T...

Page 3: ...not sent immediately but after a pre alarm time The alarm fault is tested repeatedly with period about 4 s and only after the specified number of positive tests is reached the corresponded message is...

Page 4: ...Set check the configurable parameters of all UWI IQ in installation system 6 Choose the best place to fix the UWI IQ unit with regards to an easy connection with the source of the input signal and or...

Page 5: ...ble flashes each delay step since the message has been received When the button is pressed during the running output delay or RESET message or possibly Q message if enabled is received no change of ou...

Page 6: ...is indicated only if all samples in queue are tested as active If any sample in this pre alarm period is tested as normal the number of tested samples in queue is reset Default set is 2 samples The op...

Page 7: ...pressed shortly or T message received Press the pushbutton shortly to TEST stop the detector gets into NORMAL and R message will be sent The TEST will be stopped after receiving of r message If no but...

Page 8: ...The UWI IQ is trying to estimate the user intention and if the UWI IQ is in other status than normal a simple short press and release of the detector button can be the first easy solution of the most...

Page 9: ...Test Leds is lighting test message T is sent by SPI and forwarded by the radio module The radio communication range can be tested this way By long press of the TEST RESET push button till lit of both...

Page 10: ...output in fire condition increased current of the loop to alarm value until receiving of stop alarm s reset r quit q _ if enabled or hush h _if enabled message or quit by a short TEST RESET button pre...

Page 11: ...ion byte CFG with following meanings of single bits CFG Configuration byte structure FIN ALARM INPUT CONFIGURATION 0 NO input active if closed 1 NC input active when open EIN FAULT INPUT CONFIGURATION...

Page 12: ...OL is not necessary more The switch at the position J3 on the terminal board allows to choose between IFC and IMC control panels and the loop current is switched to a correspondent standby level autom...

Reviews: