Description

 

 

Universal wireless interface UWI-IQ can serve either as a node of the ICAS 
wireless IQ system with uCU-IQ control panel or two UWI-IQ units can be 
used for wireless link, which is independent on IQ system. 

 

The communication protocol is compatible with the ICAS IQ system. The 
UWI-IQ is supposed to be powered from the device which is connected to 
or from uPU-IQ. There are wide possibilities  of user  configurations 
available, which allows to adapt the UWI-IQ to specific user application. 
The configuration is designed  as wireless and user friendly special PC 
application -  part of the RF monitor software tool, which serves for ICAS 
wireless system configuration and monitoring.  

 

 
Wireless  link  is able  to  secure  transmission  of  two  input  signals  from  one 
UWI-IQ unit by wireless to two relay outputs and loop option of the second 
UWI-IQ  unit,  which  are  configured  into  a    wireless  link.  (peer  to  peer 
system configuration)

 

The UWI-IQ inputs are supposed to be connected to potential-free contacts  
and can be configured as NC or NO which is possible to set for each input 
individually.

 

( typically relay outputs of IRS-3 or control panels or open collector outputs 
possibly).  The  corresponded  alarm/fault  message  is  sent  after  the  contacts 
connected to UWI inputs are switched on (NO config.) / switched off (NC 
config.). After its releasing/ connecting is sent the corresponded stop alarm/ 
stop fault message then.

 

 
UWI-IQ  allows  to  indicate  power  supply  on  by  green  LED,  activity  on 
inputs  and  running  pre-alarm  (inputs  delay)  or    outputs  delay  from  the 
remote  alarm/failure  message    by  yellow  and  red  LEDs  -  the  red  LED 
serves also for Test indication. 

 

The  next  two  LEDs  serve  for  indication  of  received  messages  (remote 
events) at the same time with relevant outputs activity.

 

 
Fire  ALARM relay is activated after receiving of the fire alarm message - 
the  loop  optional  output  will  increase  the  current.  The  FAULT  relay  is 
activated after receiving of the fault message.  

 

It  is  possible  to  set  in  UWI-IQ  configuration  the  outputs  /  relays  response 
also  to  local  events  and  also  it  is  possible  to  set  delay  of  the  output  after 
alarm/fault message receiving.

 

 If  a  control  panel  wired  loop  is  connected  to  the  UWI-IQ  loop  terminal 
instead of EOL resistor, the normal loop current flows through the UWI-IQ 
in normal condition. There are available two different levels of the normal 
loop  current  -  corresponds  to  IMC-Mx  panels  or  to  IFP-2.32  panel.  The 
switch  on  position  J3  on  the  UWI-IQ  Terminal    board  serves  for  an  easy 
choice of the required  normal loop current level. 

 

The  UWI-IQ  will  increase  the  loop  current  after  the  fire  alarm  message 
receiving to the fire alarm level, for the connected control panel. 

 

The  fault  is  indicated  by  interruption  of  the  loop  after  fault  message 
receiving - the loop current gets down and it will affect loop fault indication 
on the connected control panel. 

 

(Typically application - transmission of FIRE ALARM and FAULT signals 
between  two  UWIs,    -  for  example  from  remote  IRS-3  aspiration  detector  
to a standard ICAS control unit - IMC-MD, IFP2.32 etc.)

 

The same  kind of UWI-IQ model can serve either as wireless transmitter or 
receiver or  as a node of ICAS IQ system on the detector level.

 

 
UWI-IQ unit can serve also as an universal interface for  ICAS   IQ system 
with  uCU-IQ  control  panel(s).  In  this  configuration    the  UWI-IQ  unit 
occupies  one detector position in the system configuration. 

 

There  is  an  easy  adjustable  delay  available  for  fire  alarm  and  fault 
messages.   After appearing of alarm  condition on an input, the message is 
not  sent  immediately,  but  after  a  pre-alarm  time.  The  alarm/fault  is  tested 
repeatedly  with  period  about  4  s  and  only  after  the  specified  number  of 
positive tests is reached, the corresponded message is transmitted. 

 

 
The  required    pre-alarm  period  (input  delay)  is  easy  adjustable  by  user  in 
steps  about  4s.  The  easy  way  to  set  is  to  use  the    RF-monitor  and  set  the 
required delay in the UWI-IQ configuration page.

 

The stop alarm/ stop fault messages are not delayed.

 

 
The  UWI-IQ  is  able  to  send  and  receive  both  alarm  and  fault  signals 
sequentially.  In  case  the both alarm and  fault  signal  are  received,  the  both 
relays  are  activated and the  alarm status has   priority  on  the  loop  optional 
output. 

 

 

It is possible to set also an output delay, which is an adjustable delay 
between receiving of the alarm or failure message and a correspondent 
output activities. This delay is user adjustable from the  UWI-IQ 
configuration page of the RF - monitor.

 

 

 

 

 

Testing & Delay setting.

 

 

The UWI-IQ can be tested  by the TEST button. It is possible to test the  
radio-communication this way- short press of the test button evokes 
transmitting of the Tests / Reset message depends on current UWI-IQ 
status  -  normal /  test mode.

 

The UWI-IQ gets from normal to test mode either by test button activity 
or after receiving of the test message from another component in 
wireless system configuration. 

 

As soon as the Test mode is enabled, the outputs of the  UWI-IQ unit 
will follow its  inputs, which allows to test the hardware easy. The 
transmitting of  alarm/failure  messages is kept in the  test mode too.  

 

The test mode can be stopped by the  Test button or by receiving of the  
reset message.

 

Test mode will be  reset automatically in about  3 minutes if any reset 
message or button activity is not coming.

 

 

 

The response to the  alarm/ fault events on UWI-IQ inputs can be 
delayed. The delay of the correspondent message sending is determined 
by number of input tests after the  input signal level change from normal  
to alarm / fault  condition. 

 

The response to the alarm/fault disappearing  ( to the change of the 
signal level to normal level ) is not delayed.

 

The default value of the delay is set to  2  (2 samples = 2 x  4s)

 

The delay ( number of samples) is possible to change or check by PC 
with RF monitor software .

 

UWI-IQ allows   an alternative set of  a new input delay  without  PC 
assistance  by a long press of the Test button. For the new delay set 
press the test button till appears the long yellow LED light and 
following required number of red flashes . 

 

 Every red flash during this  set up routine means  an  incrementing of 
the number of  signal samples  between input change and message 
sending (Increasing of the delay with next 4s.)

 

You can check the current  delay easy by an intended  shortage of an 
UWI-IQ input and  counting of flashes during the pre-alarm time.

 

 
The output delay is possible to set/change  only from the RF-monitor , 
the default set is 0. If an output delay is set, the indication of the output 
delay will start after alarm/fault message receive by double flash of red 
or yellow LEDs (depends on received message  F or E)  with period 
about 4s. After the output delay time-out the double flashes stopped and 
UWI-IQ gets to the standard event indication and correspondent relay 
and loop output is activated.

 

 

 

Terminal description:

 

 
There are two terminal lines at the UWI-IQ -Term board.

 

(The terminals are marked directly by their function - the numbers 
used in this description are not on the PCB print)

 

 
INPUT terminal line:

 

 

1       - POWER  

 

 (    0V        - power supply input)

 

2    + POWER 

 

 9-12V DC - power supply input

 

3

 

4

 

5    INP  2  0V  (Fault) 

 signal input pot.free contact or 0V for 

OC

 

6    INP  2  E    (Fault) 

 signal input potential free contact or 

OC 

 

7    INP  1  0V (Fire) 

 signal input pot.free contact or 0V for 

OC

 

8    INP  1  E    (Fault) 

 signal input potential free contact or 

OC

 

 
 
 

Summary of Contents for UWI-IQ

Page 1: ...UWI IQ manual rev 5 07 2019 Page 1 12...

Page 2: ...UWI IQ manual rev 5 07 2019 Page 2 12 UWI IQ Universal wireless interface in the band 868 MHz Universal wireless link UWI IQ to UWI IQ D R A F T...

Page 3: ...not sent immediately but after a pre alarm time The alarm fault is tested repeatedly with period about 4 s and only after the specified number of positive tests is reached the corresponded message is...

Page 4: ...Set check the configurable parameters of all UWI IQ in installation system 6 Choose the best place to fix the UWI IQ unit with regards to an easy connection with the source of the input signal and or...

Page 5: ...ble flashes each delay step since the message has been received When the button is pressed during the running output delay or RESET message or possibly Q message if enabled is received no change of ou...

Page 6: ...is indicated only if all samples in queue are tested as active If any sample in this pre alarm period is tested as normal the number of tested samples in queue is reset Default set is 2 samples The op...

Page 7: ...pressed shortly or T message received Press the pushbutton shortly to TEST stop the detector gets into NORMAL and R message will be sent The TEST will be stopped after receiving of r message If no but...

Page 8: ...The UWI IQ is trying to estimate the user intention and if the UWI IQ is in other status than normal a simple short press and release of the detector button can be the first easy solution of the most...

Page 9: ...Test Leds is lighting test message T is sent by SPI and forwarded by the radio module The radio communication range can be tested this way By long press of the TEST RESET push button till lit of both...

Page 10: ...output in fire condition increased current of the loop to alarm value until receiving of stop alarm s reset r quit q _ if enabled or hush h _if enabled message or quit by a short TEST RESET button pre...

Page 11: ...ion byte CFG with following meanings of single bits CFG Configuration byte structure FIN ALARM INPUT CONFIGURATION 0 NO input active if closed 1 NC input active when open EIN FAULT INPUT CONFIGURATION...

Page 12: ...OL is not necessary more The switch at the position J3 on the terminal board allows to choose between IFC and IMC control panels and the loop current is switched to a correspondent standby level autom...

Reviews: