ICAS UWI-IQ Manual Download Page 6

 

 

 

Test 

Press the test button shortly  (till red led TEST gets on) - the UWI-IQ gets into the test mode, red LED  indicates Test and the message 'T' is sent to other  
nodes. 
As soon as the  other  UWI-IQ  in the wireless link or other UWI-IQ and CHOR-IQ detectors into the wireless system receive this message they will get into 
the test mode too. 
The further short press of the test button will stop the Test mode and Reset message 'R' is sent to stop Test mode in remote nodes of system. 
The test mode will stopped also when R message  has been received or automatically after about 3 minutes. 

 
Diagnostic mode - hardware tests.

 

Press the button as long till both red and yellow  LEDs are lighting together.

 

The diagnostic mode is indicated by periodical flashes of red and yellow LEDs at the same time 

 

Local alarm/fault will activated local Loop output and ALARM/FAULT relay regardless the configuration set in diagnostic mode.

 

Press the button shortly for diagnostic mode stop. 

 
Power supply

 

The UWI-IQ unit is supposed to be powered  through the POWER ter/- from an external power supply (in case of the UWI-IQ to UWI-IQ link it is 
powered mostly from the control panel or IRS-3 which is the UWI-IQ connected to). If the UWI-IQ unit is used as a node of the system with uCU-IQ, the uPU 
power supply can be used also for UWI-IQ energizing.  The power supply is indicated by greed LED on the UWI-IQ panel  
The power supply voltage loss will be indicated by switch off of the green LED on UWI-IQ panel and after communication test period expiration  also as a 
communication fault on uCU-IQ control panel.  

 

Software description:

 

The UWI-IQ unit is controlled by ICAS software application which is installed into the ATTINY44A, this software has been  designed in ATMEL assembler 
language and cooperates with the second ICAS application software which is designed in C language and programmed into IQRF radio-module and on 
background  of this application is running the IQRF OS. The UWI-IQ takes advantage of use of the same application software of IQRF radio-module

 

The ATTINY software controls the timing of processes and switch between standby mode with very low current consumption and active mode which is 
activated periodically by watchdog wake up technique.

 

 
Advanced Digital Signal-filtration (ADS)

 

The UWI-IQ software solution guarantees a correct signal handling and reduce nuisance of false alarms and give improved immunity against EM noise. In case  
of important events, i.e. alarms and faults, can be the UWI-IQ input signals tested repeatedly in queue of samples which number is possible to set by 
configuration option and the alarm or fault is indicated only if all samples in queue are tested  as active. If any sample in this pre-alarm period is tested as 
normal, the number of tested samples in queue is reset. (Default set is 2 samples)

 

The optional delay between received message and relevant output change can be set in addition. The receiving message is indicated during the running delay 
period and allows possible action of the user   before  UWI-IQ outputs activation. (Default set is 0)

 

 
 
The software of the interface microcontroller serves for following tasks:

 

• 

input signal processing (digital filtering)  - the similar   signal  filtration as in ICAS CHOR-IQ is used

 

• 

update of two status words - the first serves for the  internal interface status, the second one for the loop status

 

• 

generation of the output message for wireless loop depends on actual interface status

 

• 

wake up of the radio-module and control the data /message/ exchange between radio-module and interface

 

• 

SPI master for communication between radio-module and the in built interface microcontroller

 

• 

received message analysis and loop status word update

 

• 

indication of the UWI-IQ status

 

• 

indication of the  link status -  remote events  indication by LEDs, relays and Loop output control 

 

• 

test processing and  indication

 

• 

memory check and system error indication

 

• 

pushbutton interrupt processing and intelligent response to pushbutton activity which depends on current detector and loop status

 

• 

input delay adjustment (filtering set)

 

 

The software of the radio-module serves for the following tasks:

 

• 

Operation for joining or deleting from the specific loop, loop creating - learn mode indication

 

• 

Wake up from the SPI master and communication in SPI SLAVE mode with UWI-IQ interface  (the new message is sent from radio-module into the 
interface and  a new message from the interface is sent into the radio-module at the same time) 

 

• 

Timing of transmitting time slots for wireless communication depends on its loop number in order to avoid communication  collisions in one loop

 

• 

Transmitting of the message from the interface  into the loop or to the IQ control panel (depends on IQ System configuration)

 

• 

Loop Message monitoring, processing and selection (the message from the loop is not automatically sent directly to the UWI-IQ)

 

 

 
 
 
Indication

 

 

There are one green, two red and two yellow LEDs for indication on the panel.

 

 
The green  LED  

(POWER)  

serves only for the power supply indication.

 

 
Red LED  (LOCAL ALARM/TEST) 

it serves for indication of the local pre-alarm by flashing and following steady indication of full  local alarm 

 

 

 

 

it serves for the indication of the output delay after receiving of the F message (before Fire output activation)

 

 

 

 

 

it serves also for indication of TEST mode after receiving of T message or after TEST button short press 

 

 

 

 

 

it serves also for indication of the new input delay, during manual delay adjustment procedure

 

 

 

Summary of Contents for UWI-IQ

Page 1: ...UWI IQ manual rev 5 07 2019 Page 1 12...

Page 2: ...UWI IQ manual rev 5 07 2019 Page 2 12 UWI IQ Universal wireless interface in the band 868 MHz Universal wireless link UWI IQ to UWI IQ D R A F T...

Page 3: ...not sent immediately but after a pre alarm time The alarm fault is tested repeatedly with period about 4 s and only after the specified number of positive tests is reached the corresponded message is...

Page 4: ...Set check the configurable parameters of all UWI IQ in installation system 6 Choose the best place to fix the UWI IQ unit with regards to an easy connection with the source of the input signal and or...

Page 5: ...ble flashes each delay step since the message has been received When the button is pressed during the running output delay or RESET message or possibly Q message if enabled is received no change of ou...

Page 6: ...is indicated only if all samples in queue are tested as active If any sample in this pre alarm period is tested as normal the number of tested samples in queue is reset Default set is 2 samples The op...

Page 7: ...pressed shortly or T message received Press the pushbutton shortly to TEST stop the detector gets into NORMAL and R message will be sent The TEST will be stopped after receiving of r message If no but...

Page 8: ...The UWI IQ is trying to estimate the user intention and if the UWI IQ is in other status than normal a simple short press and release of the detector button can be the first easy solution of the most...

Page 9: ...Test Leds is lighting test message T is sent by SPI and forwarded by the radio module The radio communication range can be tested this way By long press of the TEST RESET push button till lit of both...

Page 10: ...output in fire condition increased current of the loop to alarm value until receiving of stop alarm s reset r quit q _ if enabled or hush h _if enabled message or quit by a short TEST RESET button pre...

Page 11: ...ion byte CFG with following meanings of single bits CFG Configuration byte structure FIN ALARM INPUT CONFIGURATION 0 NO input active if closed 1 NC input active when open EIN FAULT INPUT CONFIGURATION...

Page 12: ...OL is not necessary more The switch at the position J3 on the terminal board allows to choose between IFC and IMC control panels and the loop current is switched to a correspondent standby level autom...

Reviews: