Uninterruptible power-supply environment requirements
An uninterruptible power-supply environment requires that certain specifications
for the physical site of the SAN Volume Controller must be met.
2145 UPS-1U environment
All SAN Volume Controller models are supported with the 2145 UPS-1U.
2145 UPS-1U specifications
The following tables describe the physical characteristics of the 2145 UPS-1U.
2145 UPS-1U dimensions and weight
Ensure that space is available in a rack that is capable of supporting the 2145
UPS-1U.
Height
Width
Depth
Maximum weight
44 mm
(1.73 in.)
439 mm
(17.3 in.)
579 mm
(22.8 in.)
16 kg
(35.3 lb)
Note:
The 2145 UPS-1U package, which includes support rails, weighs 18.8 kg (41.4 lb).
Heat output
The 2145 UPS-1U unit produces the following approximate heat output.
Model
Heat output during normal
operation
Heat output during battery
operation
2145 UPS-1U
10 W (34 Btu per hour)
150 W (512 Btu per hour)
Power cables for the 2145 UPS-1U
If you do not connect the 2145 UPS-1U to a rack power distribution unit (PDU) or
redundant ac-power switch, you must follow your country or region’s power
requirements to choose the appropriate power cable for the 2145 UPS-1U.
The 2145 UPS-1U is supplied with an IEC 320-C13 to C14 jumper to connect it to a
rack PDU. You can also use this cable to connect the 2145 UPS-1U to the redundant
ac-power switch.
The following table lists the power cable options for your country or region.
Country or region
Length
Connection type
(attached plug
designed for 200
- 240 V ac
input)
Part number
United States of America (Chicago),
Canada, Mexico
1.8 m (6 ft)
NEMA L6-15P
39M5115
Chapter 3. Uninterruptible power supply
27