2: Period/frequency on
A / B / AB pulses
PeriodTime
ABDirection
Frequency
DINT
DINT
REAL
Period and frequency are measured accord-
ing to „quadrature mode“
All 4 edges (pos.A, neg.A, pos.B, neg.B) are
processed, i. e. the measured frequency is
four times as high as the real frequency,
the period time decreases accordingly by
factor 4.
PeriodTime is the period duration in ns.
ABDirection
ABDirection = 0
A-pulse before B-pulse
ABDirection = 1
B-pulse before A-pulse
Frequency is given in Hz.
3: Pulse width / duty cy-
cle on A
PeriodTime
PulseWidth
DutyCycle
DINT
DINT
REAL
Refers solely to signal A.
PeriodTime is the period duration in ns.
PulseWidth is the positive pulse width of A.
DutyCycle is the duty factor between high-
und low-level (DutyCycle[0..1])
4: Up/down counter of
A / B pulses
Counter
DINT
Counts edges accord
ing to the „quadrature
m
ode“
Counts all 4 edges of A and B (pos.A,
neg.A, pos.B, neg.B).
When A-pulse is before B-pulse the analysis
counts up, when B-pulse is before A-pulse it
counts down.
„Reset on N“ is active
„Divide by 4“ is not active
The following table shows the adjusted parameters:
Analysis
regulation
1: Pulse
counter
2: Period / fre-
quency
3: Pulse width
/ duty cycle
4: Up/down
counter
Mode
Q
Q
D
irect
Q
uadrature
S
ign
al
edg
e
pos. A
●
8
●
High
level
●
neg. A
●
●
●
pos. B
●
●
●
neg. B
●
●
●
F
u
n
ctio
n
„Divide by 4“
▬
„Reset on N“
●
●
„B as qualifier“
8