Connecting Accessory Devices
Revision C
Smart DC Controller
4-11
8VHU5HOD\V3URJUDPPLQJ3URFHGXUH
The Smart DC Controller is able to interface with many types of external devices through the use of two user-
programmable output relays. All of the user relay functions identified and described in Table 4-3 are accessible
in the Installer Menu.
127(
The User Relays will operate normally to less than 18VDC. The USER 2 RELAY is rated for
DC only up to 48V and does not have a N.C. (normally closed) connection.
Use the Smart DC Controller buttons to program the user relays according to the following steps:
1. Select and connect to the relay you wish to use on the Smart DC Controller board.
2. Access the Installer Menu and RL 1 or RL 2 display (depending on the relay you have connected).
3. Enter the appropriate function using the associated number (1 through 24) listed in the table.
7DEOH8VHU3URJUDPPDEOH8VHU5HOD\V)XQFWLRQ2SWLRQV
No.
Name
Description
1
Close limit output
Creates an interlock signal to another operator’s interlock input, or simply to indicate that the
gate is secure. The relay is released when the fully-closed limit switch is tripped. The relay is
energized when the fully-closed limit is released. (Any open command energizes the relay.)
2
Close limit pulse output
Used in a sequenced system to command a second machine to close. Generates a brief pulsed
output that occurs when the close limit is triggered.
3
Open limit output
Indicates a full-open position. This output becomes active when an open-limit is triggered
and releases when the open-limit is released.
4
Open limit pulse output
Trips a sequenced barrier arm gate operator to open. Generates a brief pulsed-output when
the open-limit is triggered. An additional pulse is also generated with any new open command
even when the gate is already fully-opened.
5
Warn before/during operate
output
Controls an external warning device. This output operates at the same time as the internal
warn before operate buzzer.
6
Gate Lock output
Controls external solenoid locks or magnetic locks. In both directions of travel, this output is
activated about 7/10
ths
of a second before the operator starts moving the gate and remains
active while moving as well as for a few seconds after stopping.
7
Gate forced open output
Activated if the gate is forced off the closed limit switch and operator is not able to restore the
gate to full closed within four seconds. This alarm resets itself in 30 seconds.
8
Gate open too long output
Activates when the gate is open longer than a user-selected period of time. Adjustable from 0
delay to 135 seconds delay in 30-second time increments.
Note:
TL - OPEN TIME ALERT adjustments can be made in the Installer Menu.
9
Safety Mode Alert output
Activated when system is in Safe Mode or entrapment mode.
10
Entrapment Mode Alert output
Activated only when system is in the Entrapment Mode.
11
Unauthorized Vehicle Entry
output
Activated when a second vehicle enters from the outside without a valid input from an access
control device. This output releases when an access control input signals open or the gate
reaches the close limit position.
12
Outside Obstruction Vehicle
Detector output
Interlocks an entry device to prevent pedestrian use. This output is active whenever the
Outside Obstruction Loop Detector is tripped.