iRIS 350FX Reference Manual V1.50
29
HyQuest Solutions (NZ) Ltd
- PO Box 9466, Hamilton, New Zealand Tel: +64 7 857-0810 Email: [email protected]
Write Timeout:
Number of minutes to wait for lack of write from master before setting sensor locations to either NaN for
floating point sources and Invalid Value (see below) for integer sources. Setting the timeout to zero will
disable this feature
Invalid Value (for 2 Byte):
This is the value that will be substituted for 2 byte sort registers when there is a communications timeout
(see Write Timeout above).
I/O Configuration
6.3.4.1
Digital Ins/Outs
This menu is used to configure digital input and output.
Output Mode:
Choose the operating mode of the output from the available options. Valid digital output modes are:
Table 2 – Digital Output Modes
Mode
Description
Disabled
The Digital I/O channel will operate as a digital input.
Schedule
Follows the schedule as defined by the settings.
Schedule Plus
Follows the schedule as defined by the settings. Also activate the output when a user is
logged in or an RS232 Telemetry mode call-in is in progress. If a user is logged on via
the LCD/keypad interface OR the power mode is set to RS232 Telemetry and an alarm
requiring transmission to a base station is pending, the output will be on.
Alarm
The output is on if any sensor alarm is active. Turns off when all alarms are inactive.
Remote
Remote Control from HydroTel or via a custom script. DIO1 is controlled by bit 0 of
d1000, DIO2 by bit 1 of d1000, DIO3 by bit 2 of d1000 and DIO4 by bit 3 of d1000.
Online
Follow wireless link state i.e. the output is on if the wireless modem is on-line.