Page 30
Step
Action
1
Unscrew and remove the transparent cover of the pressure switch
(permeate).
2
Set the switch-off pressure with the control dial on the pressure
switch (permeate).
The pressure switch (permeate) has an adjustment range of
1 to 3.5 bar.
The control dial is restricted by an endstop:
•
White control dial fully turned to the right: pressure switch set to
1 bar
•
White control dial fully turned to the left: pressure switch set to
3.5 bar
Fig. 9: Control dial endstop of pressure switch(Permeate)
When the required pressure is achieved in the system to be filled, the
system
switches off automatically
via the pressure switch
(permeate).
The system
switches back on again automatically
when the
pressure in the system to be filled has dropped by approx. 0.5 bar.
3