Page 53
6.8.13 Recording submenu
The control can record 10 data sets internally
on a rolling basis ("Recording" submenu,
parameter 1 set to "ON"). Snapshots of the
unit status are carried out at intervals of 10 s,
which can be helpful for troubleshooting.
When all memory slots are filled, a new data
set overrides the oldest entry. A stored data
set is retained for maximum of 7 days.
The complete recording [93] can be saved to
a USB stick with NTFS formatting.
The procedure is as follows:
»
Open the "Recording" submenu.
»
Set the "Save recording" parameter
(2) to "On".
Insert the USB stick into the socket on the
mainboard (see diagram below). Saving
starts automatically. Afterwards, the setting of
the "Save recording" parameter reverts to
"Off".
The
status
can be checked by calling up the
"Saving status" parameter (4). “Enabled"
means that the write operation is active.
The entire storage can be
deleted
using the
"Delete recording" parameter (5).
A data set consists of the following values:
USB connection on mainboard
No.
Value
only
1
Steam_actual_unit
2
Steam_actual_Cyl. 1
DZG
3
Steam_actual_Cyl. 2
DZG
4
Status_unit
5
Status_cyl. 1
6
Status_cyl. 2
DZG
7
Fault message_unit
8
Fault message_cyl. 1
9
Fault message_cyl. 2
DZG
10
Safety interlock_open
11
Demand
12
Steam_output_max.
13
Current_actual_Cyl. 1
ELDB
14
Current_actual_Cyl. 2
ELDB DZG
15
Water_level_cyl. 1
HKDB
16
Water_level_cyl. 2
HKDB DZG
21
Temp._actual value
22
Temp._actual_value 1
2S
23
Temp._actual_value 2
2S
24
Temp._set value
Legend:
ELDB = Electrode Steam Humidifier
HKDB = Heater Element Steam Humidifier
DZG = Double Cylinder Unit
2S = Device featuring 2 Temperature Sensors